156
Serial communications
ACH550-01 User's Manual
Analogue output signal source selection
1410
…
1412
RELAY OUTPUT 4…6
0…47
Defines the event or condition that activates relay 4…6 – what relay
outputs 4…6 means.
• See 1401
RELAY
OUTPUT
1.
Code Setting for fieldbus control & description Range
1501
AO1 CONTENT SEL
99…178
Defines the content for analogue output AO1.
135 = c
OMM
VALUE
1 – Energise output based on the input from fieldbus
communication (parameter 0135).
136 = c
OMM
VALUE
2 – Energise output based on the input from fieldbus
communication (parameter 0136).
1502
AO1 CONTENT MIN
-
Sets the minimum
content value.
• Content is the
parameter
selected by
parameter 1501.
• Minimum value
refers to the
minimum content
value that will be
converted to an
analogue output.
• These
parameters
(content and
current min. and
max. settings)
provide scale
and offset
adjustment for
the output. See
the figure.
1503
AO1 CONTENT MAX
-
Sets the maximum content value
• Content is the parameter selected by parameter 1501.
• Maximum value refers to the maximum content value that will be
converted to an analogue output.
1504
MINIMUM AO1
0.0…20.0 mA
Sets the minimum output current.
Code Setting for fieldbus control & description Range
AO (mA)
AO
CONTENT
P 1504 /
P 1502/1508
P 1503/1509
AO (mA)
AO
CONTENT
P 1505 /
P 1504 /
P 1503/1509
P 1502/1508
P 1505 /
P 1511
P 1510
P 1511
P 1510