340
Parameter listing and descriptions
ACH550-01 User's Manual
HVAC
default
Supply fan Return fan
Cooling
tower fan Condenser
Booster
pump
Parameter
name
Par.
index
1
2
3
4
5
6
15 ANALOGUE
AO1
CONTENT
SEL
1501
OUTPUT
FREQ
OUTPUT
FREQ
OUTPUT
FREQ
OUTPUT
FREQ
OUTPUT
FREQ
OUTPUT
FREQ
OUTPUTS
AO1
CONTENT
MIN
1502
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
AO1
CONTENT
MAX
1503
50.0 Hz
50.0 Hz
50.0 Hz
50.0 Hz
50.0 Hz
50.0 Hz
MINIMUM AO1 1504
4.0 mA
4.0 mA
4.0 mA
4.0 mA
4.0 mA
4.0 mA
MAXIMUM
AO1
1505
20.0 mA
20.0 mA
20.0 mA
20.0 mA
20.0 mA
20.0 mA
FILTER AO1
1506
0.1 s
0.1 s
0.1 s
0.1 s
0.1 s
0.1 s
AO2
CONTENT
SEL
1507
CURRENT CURRENT CURRENT CURRENT CURRENT CURRENT
AO2
CONTENT
MIN
1508
0.0 A
0.0 A
0.0 A
0.0 A
0.0 A
0.0 A
AO2
CONTENT
MAX
1509
Defined by
par. 0104
Defined by
par. 0104
Defined by
par. 0104
Defined by
par. 0104
Defined by
par. 0104
Defined by
par. 0104
MINIMUM AO2 1510
4.0 mA
4.0 mA
4.0 mA
4.0 mA
4.0 mA
4.0 mA
MAXIMUM
AO2
1511
20.0 mA
20.0 mA
20.0 mA
20.0 mA
20.0 mA
20.0 mA
FILTER AO2
1512
0.1 s
0.1 s
0.1 s
0.1 s
0.1 s
0.1 s
16 SYSTEM
RUN ENABLE
1601
NOT SEL
DI2
DI2
DI2
DI2
DI2
CONTROLS
PARAMETER
LOCK
1602
OPEN
OPEN
OPEN
OPEN
OPEN
OPEN
PASS CODE
1603
0
0
0
0
0
0
FAULT RESET
SEL
1604
KEYPAD
KEYPAD
KEYPAD
KEYPAD
KEYPAD
KEYPAD
USER PAR
SET CHG
1605
NOT SEL
NOT SEL
NOT SEL
NOT SEL
NOT SEL
NOT SEL
LOCAL LOCK
1606
NOT SEL
NOT SEL
NOT SEL
NOT SEL
NOT SEL
NOT SEL
PARAM SAVE
1607
DONE
DONE
DONE
DONE
DONE
DONE
START
ENABLE 1
1608
DI4
DI4
DI4
DI4
DI4
DI4
START
ENABLE 2
1609
NOT SEL
DI5
DI5
DI5
DI5
DI5
DISPLAY
ALARMS
1610
NO
NO
NO
NO
NO
NO
PARAMETER
VIEW
1611
DEFAULT
DEFAULT
DEFAULT
DEFAULT
DEFAULT
DEFAULT
FAN
CONTROL
1612
AUTO
AUTO
AUTO
AUTO
AUTO
AUTO
FAULT RESET 1613
DEFAULT
DEFAULT
DEFAULT
DEFAULT
DEFAULT
DEFAULT
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com