CI 773F PROFIBUS-DP Master Interface
Section 3 Modules
38
M&I – AC 900F Controller
LED status displays
After having been switched on, the CI 773 PROFIBUS module performs a self-test
during power-up. During initialization, with newly configured modules or after a
change of the operating mode, all LEDs may light up briefly before reaching the
defined status.
Number of slaves
125
Controller redundancy support
Yes
Hot plug
Yes
HCIR
Yes
LED
Color
Status
Meaning
PWR
Green
ON
Module in operation and must not be removed
OFF
Module not in operation and may be removed, if re-
quired
STA
Green
ON
Active module operating properly
OFF
Module start-up
Orange ON
Module identified by the CPU module, but not active
Red
ON
Module error
RUN
Green
ON
Module has taken over the PROFIBUS master func-
tion
OFF
Module inactive relative to the PROFIBUS
Green
200 ms
pulse
Module ready to take over the master function
LED L Green
ON
Bus traffic
OFF
No bus traffic
Содержание AC 900F
Страница 2: ......
Страница 3: ...Freelance 2016 Mounting and Installation Instructions AC 900F Controller ...
Страница 58: ...CP C MM messaging module Section 3 Modules 58 M I AC 900F Controller ...
Страница 70: ...TB 870F terminal block Section 4 Accessories 70 M I AC 900F Controller ...
Страница 98: ...Controller configuration via terminal program Section 7 Commissioning 98 M I AC 900F Controller ...
Страница 122: ...Update Restore Section 8 Service 122 M I AC 900F Controller ...
Страница 131: ...Section 9 Technical Data CI 773F M I AC 900F Controller 131 Approvals cULus UL Class 1 Div 2 Groups A B C D EAC ...
Страница 152: ...CP A CM Section 9 Technical Data 152 M I AC 900F Controller ...
Страница 154: ...Index 154 M I AC 900F Controller ...
Страница 155: ......