Switch-mode power supply units CP-C 24/5.0 and CP-C 24/10.0
Section 3 Modules
50
M&I – AC 900F Controller
Parallel operation, increase in capacity
For “n” number of power supply units connected in parallel the output current can
be increased to “n x Ir”. A parallel connection is recommended if the power supply
unit is not rated to provide the power required for the most powerful consumer load.
In this case, the consumer load should be supplied by several independent power
supply units. Up to max. 5 devices of identical type can be connected in parallel.
CP_C24_parallel_operation_capacity.png
Parallel operation, redundancy
Redundant circuits are used to increase the operational reliability of the system in
case of errors (e.g. incorrect wiring, fuse trip in primary circuit, failure of individual
devices). If a fault occurs in the first power supply circuit (referred to as initial
fault), all loads are supplied by the second redundant circuit. For this purpose, the
power supply units connected in parallel are rated such as to ensure that the total
power requirements of all loads can be entirely covered by a single power supply
unit.
CP_C24_parallel_operation_redundancy.png
Содержание AC 900F
Страница 2: ......
Страница 3: ...Freelance 2016 Mounting and Installation Instructions AC 900F Controller ...
Страница 58: ...CP C MM messaging module Section 3 Modules 58 M I AC 900F Controller ...
Страница 70: ...TB 870F terminal block Section 4 Accessories 70 M I AC 900F Controller ...
Страница 98: ...Controller configuration via terminal program Section 7 Commissioning 98 M I AC 900F Controller ...
Страница 122: ...Update Restore Section 8 Service 122 M I AC 900F Controller ...
Страница 131: ...Section 9 Technical Data CI 773F M I AC 900F Controller 131 Approvals cULus UL Class 1 Div 2 Groups A B C D EAC ...
Страница 152: ...CP A CM Section 9 Technical Data 152 M I AC 900F Controller ...
Страница 154: ...Index 154 M I AC 900F Controller ...
Страница 155: ......