CP-C 24/10.0
Section 9 Technical Data
144
M&I – AC 900F Controller
Mechanical data
Electrical connection
Ambient temperature
Certificates
Dimensions W x H x D
90 x 130 x 137 mm
Weight approx.
1.34 kg
Installation
DIN rail
Mounting position
Horizontal
Minimum distance between devices
> 10 mm horizontal, > 80 mm vertical
Type of protection
IP 20
Wire size
0.2 - 2.5 mm
2
Wire type
Rigid, finely stranded with/without wire
end ferrule
Protection class
I
Operation with derating
- 25 ... +70 °C
Operation at rated current
0 ... +60 °C
Storage
- 40 ... +85 °C
Declaration of conformity
CE
Approvals
cULus
UL Class 1 Div 2 (Groups A, B, C, D)
EAC
The voltage as well as the input and output wiring must comply with the
requirements specified for Class I, Div. 2 - Article 501-10(B) (1) NEC.