Section 6 Wiring
Fuse dimensions
M&I – AC 900F Controller
89
A single power supply unit can be used for both supply voltages. The CPU module
and the I/O modules should, however, be provided with separate fuse protection. As
a matter of course, separate power supply units can also be used.
Fuse dimensions
To select the appropriate fuses for the station, the power consumption and the inrush
currents (melting integral of the upstream fuse) must be taken into account.
Module type
PM 902F and PM 901F
Power supply
L+ and M terminals
Voltage
24 V DC
Current consumption
1 A
Power consumption
24 W (entire station)
Make sure that the power supply unit used is rated for the required inrush current.
Module type
PM 902F and PM 901F
Total melting integrals
22 A
2
s
Rated current
4.0 A
Characteristic
AT high breaking capacity
Recommended fuse protection
Type
IEC/EN60127-2/V
Dimensions
Glass tube fuse, 5x20 mm
Содержание AC 900F
Страница 2: ......
Страница 3: ...Freelance 2016 Mounting and Installation Instructions AC 900F Controller ...
Страница 58: ...CP C MM messaging module Section 3 Modules 58 M I AC 900F Controller ...
Страница 70: ...TB 870F terminal block Section 4 Accessories 70 M I AC 900F Controller ...
Страница 98: ...Controller configuration via terminal program Section 7 Commissioning 98 M I AC 900F Controller ...
Страница 122: ...Update Restore Section 8 Service 122 M I AC 900F Controller ...
Страница 131: ...Section 9 Technical Data CI 773F M I AC 900F Controller 131 Approvals cULus UL Class 1 Div 2 Groups A B C D EAC ...
Страница 152: ...CP A CM Section 9 Technical Data 152 M I AC 900F Controller ...
Страница 154: ...Index 154 M I AC 900F Controller ...
Страница 155: ......