Maintenance menu
Section 8 Service
116
M&I – AC 900F Controller
Restart type.png
F1 function: Warm start
All controller data and variables are retained. Output modules indicate the set
security values.
F2 function: Cold start
All controller data are initialized. During cold start, output modules indicate first the
set security values and then the initialization values.
F3 function: Initialize
The entire user configuration is cancelled. Output modules indicate the set security
values. Restart the controller to load a new configuration.
Maintenance menu
Select the
Maintenance
menu to access the
Module exchange
,
Backup config
and
Save memory image
functions.
Maintenance screen.png