Switch cabinet
Section 6 Wiring
86
M&I – AC 900F Controller
Switch cabinet
•
Low-impedance connections between the switch cabinet, mounting plate,
earthing bar (PE) and shield bar must be provided.
•
Earth the switch cabinet doors on the sides using short and highly flexible
conductors.
•
To protect the control system against interferences, only bulbs or interference-
suppressed fluorescent/LED lamps should be used in the direct vicinity of the
control system for switch cabinet lighting.
•
If an interference immunity of 6 kV instead of 4 kV is required, the controller
must be installed in a switch cabinet and operated exclusively with the door
being closed.
Minimum distances
•
Provide for adequate distances to the switch cabinet walls, cable conduits,
adjacent devices, etc. There should be a distance of 20 mm around the
controller to all sides in order to ensure proper ventilation and electrical
insulation.
•
Horizontal installation is highly recommended. Vertical mounting is also
possible, but involves restrictions in terms of performance due to insufficient
air circulation, which causes heating of the devices.
•
When mounting the system in vertical position, mechanical stops must be
provided at the top and the bottom to protect the modules against vibrations.
For applications with high levels of vibration, the installation of mechanical
stops on the left and right sides is also recommended for horizontal mounting
in order to efficiently protect the modules against vibrations.
Reference potential
•
Ensure a uniform reference potential throughout the line and earth the complete
electrical equipment, as far as possible.
•
Install the earth conductors in star configuration to avoid the formation of
ground loops.
Содержание AC 900F
Страница 2: ......
Страница 3: ...Freelance 2016 Mounting and Installation Instructions AC 900F Controller ...
Страница 58: ...CP C MM messaging module Section 3 Modules 58 M I AC 900F Controller ...
Страница 70: ...TB 870F terminal block Section 4 Accessories 70 M I AC 900F Controller ...
Страница 98: ...Controller configuration via terminal program Section 7 Commissioning 98 M I AC 900F Controller ...
Страница 122: ...Update Restore Section 8 Service 122 M I AC 900F Controller ...
Страница 131: ...Section 9 Technical Data CI 773F M I AC 900F Controller 131 Approvals cULus UL Class 1 Div 2 Groups A B C D EAC ...
Страница 152: ...CP A CM Section 9 Technical Data 152 M I AC 900F Controller ...
Страница 154: ...Index 154 M I AC 900F Controller ...
Страница 155: ......