Building Automation |
Operation of communication objects 35
MYLOS
®
Building Automation
Operation of communication objects
3.1
Rocker switch 1/2
3.1.1 Switching rocker switch
No.
Function
Object name
Type of datum
Flags
16
Disabling
Rocker switch 1
1 bit DPT_Enable
C,W,T
23
Disabling
Rocker switch 2
1 bit DPT_Enable
C,W,T,U
The channel circuitry can be blocked or enabled using the communication object.
A blocked channel behaves as if there was no input signal. The communication
objects of the channel are still available.
17
Switching
Rocker switch 1
1 bit DPT_Switch
C,W,T
24
Switching
Rocker switch 2
1 bit DPT_Switch
C,W,T
Telegram value:
“0” OFF
“1” ON
According to parameter setting, this communication object can be switched by the ON, OFF or Switching input drive.
With Switching the previous value, for example “1”, is directly switched to value “0”. It is important to ensure that
the communication object can be written from the outside. Therefore cyclic sending is interrupted or is not possible.
34
Disabling LED
Rocker switch 1
1 bit DPT_Enable
C,W
34
Disabling LED
Rocker switch 2
1 bit DPT_Enable
C,W
The “Disabling Led” communication object makes it possible to enable (1) the LED so as that it switches
on or off depending on the operating mode selected from the parameters or to disable it (0) forcing it into a
continuous switching off status.
3.1.2 Switching rocker switch
No.
Function
Object name
Type of datum
Flags
16
Disabling
Rocker switch 1
1 bit DPT_Enable
C,W
23
Disabling
Rocker switch 2
1 bit DPT_Enable
C,W
The channel circuitry can be blocked or enabled using the communication object.
A blocked channel behaves as if there was no input signal. The communication
objects of the channel are still available.