28 Commissioning
| MYLOS
®
Building Automation
MYLOS
®
Building Automation
Commissioning
2.9
Scene rocker switch
Reaction to short pressure
After a short pressure the device will respond recalling a scene ("Recall scene") or not ("No reaction").
Store scene
This parameter determines the way in which the current scene storage begins and which function the "Store scene"
communication object has.
If “In case of long pressure” the scene is stored as soon as a long pressure command is detected and storage ends
as soon as the push-button is released.
If “With object value = 1” storage is activated as soon as the “Store scene” communication object receives value 1.
If “In case of long pressure (if object value = 1)” storage is activated as soon as a long pressure is detected and the
value of “Store scene” communication object is 1. Storage ends as soon as the push-button is released.
Long pressure: Base
Long pressure: Multiplier [0…255] (if “In case of long pressure” or if “in case of long pressure (if object
value = 1)”)
These two parameters allow you to determine the time that is sufficient to consider a pressure as a long pressure.
Time interval is calculated as follows: Period for long pressure = Base * Multiplier.