Commissioning 21
MYLOS
®
Building Automation
Commissioning
2.6
Logic function
For each output the logic function makes up to two logic objects available, that are logically connected to the
“Switching” communication object.
The parameter window is enabled in “Function”.
When receiving an object value, the logic function is always recalculated. First of all the “Logic gate 1” object is
evaluated with the “Switching” object. The result is connected to the object “Logic gate 2”.
See section 4.2.3. for explanations of the logic function.
Please examine the chart of operation of section 4.2.1.
“Logic gate x object” parameter (x = 1, 2)
The object “Logic gate 1” or “Logic gate 2” is enabled with this parameter.
Options:
-
inactive
- active
“Logic gate x object function” parameter (x = 1, 2)
Here the logic function of the “Logic gate x” object is defined together with the “Logic gate x”. Three standard
operators are available (AND, OR, XOR). The gate function is also available to lock switching commands. Setting
the “Logic gate x object” parameter to “not active”, the logic function is disabled.
Options:
- AND
- OR
- XOR
- Gate function