Fault Finding
The curtains fail to close or part close on
receipt of a fire alarm signal or test.
The curtains fail to retract fully.
• Check there has been no modifications to the ceiling or walls that could prevent
the curtain and bottom bar from deploying.
• Check the curtain security tabs are correctly positioned within the guide
channel.
• Check the bottom bar is not snagged in the guide channels by the guides being
pinched.
• Check there is a minimum tolerance in the guide channel mouth of 8mm for the
full length of the guide channel.
• Check the bottom bar has sufficient weight to deploy the curtain.
• Check the brake light on the MCC is not illuminated if so the open time is not
greater than the travel time of the curtain in the open time settings of the MCB.
• Check there is a minimum tolerance in the guide channel mouth of 8mm for the
full length of the guide channel.
• Check the curtain security tabs are not pulling through onto the guide channel
running face.
• Check there is 24volts at the MCB motor terminal and power terminal.
• Check the dip switch settings within the MCC and increase the power if required.
• Check the curtain has not snagged on the guide fixings.
65
Содержание Evo1-MCP 1
Страница 4: ...Back to contents Mechanical Installation Instructions 4...
Страница 17: ...Back to contents Control Panel Lighting 17...
Страница 20: ...Back to contents Motor Control Board Lighting 20...
Страница 22: ...Back to contents General Overview Instructions 22...
Страница 25: ...Back to contents Control Panel Wiring 25...
Страница 30: ...Back to contents Motor Control Board Wiring 30...
Страница 36: ...Back to contents Dip Switch Settings 36...
Страница 39: ...Back to contents Override Switch Wiring to Control Panel 39...
Страница 41: ...Back to contents Override Switch Wiring to Motor Control Board 41...
Страница 44: ...Back to contents Control Panel Function Programming 44...
Страница 54: ...Back to contents Optional Extras 54...
Страница 58: ...Wiring of Optional Extras 58...
Страница 64: ...Back to contents Fault Finding 64...
Страница 67: ...Back to contents Maintenance Service 67...
Страница 71: ...EVO System Maintenance Record Date Date Date Action Taken Action Taken Action Taken Engineer Engineer Engineer...
Страница 72: ...EVO System Maintenance Record Date Date Date Action Taken Action Taken Action Taken Engineer Engineer Engineer...
Страница 73: ...EVO System Maintenance Record Date Date Date Action Taken Action Taken Action Taken Engineer Engineer Engineer...
Страница 74: ...Back to contents Standard Drawings Headbox and Guides 74...
Страница 84: ...Back to contents 44 0 1204 383839 info a1shutters co uk www a1sgroup com...