Instruction manual SGS
87
Water leakage
Leakage from a water
connection (threaded)
Tighten the threaded connection
If the leak persists, consult your installation engineer
Condensate leakage
Check that the condensation water discharge is working properly.
Rectify if necessary
Leakage from another
nearby water water
heater or pipe segment
Trace the leak
Leakage from the water
heater tank
Consult the supplier and/or manufacturer
Explosive ignition
Incorrect supply
pressure and/or CO
2
Set (3.13 "Check the supply pressure, gas control valve pressure,
CO
2
value and switching pressure") the correct supply pressure
and/or CO
2
.
If ignition is not improved, consult your installation engineer.
Contaminated burner
Clean the burner (15.4.2 "Cleaning the burner")
Insufficient or no hot
water
The water heater is off Start the water heater (9 "Starting the water heater")
No supply voltage
present
1. Check whether the isolator is ON.
2. Check that there is power to the isolator.
3. Check whether the ON/OFF switch of the controller is ON
(position I).
4. Check whether there is power to the electrical connector block.
5. The measured voltage must be 230 V
AC
(-15%, +10%)
See the electrical diagram (17 "Appendices").
If the error persists, consult your installation engineer.
Hot water supply is
used up
Reduce hot water consumption and give the water heater time to
heat up.
If there continues to be insufficient or no hot water, consult your
installation engineer.
The controller is in the
OFF position.
Switch the controller to the ON position (11.3 "Switching to "ON
mode"").
Temperature (T
set
) is
set too low.
Set temperature (T
set
) to a higher setting (11.4 "Setting the water
temperature").
Indication
Cause
Measure
Remark
Содержание SGS - 100
Страница 7: ...4 Instruction manual SGS gis...
Страница 11: ...Contents 8 Instruction manual SGS...
Страница 23: ...Working principle of the water heater 20 Instruction manual SGS 2 gis...
Страница 37: ...Installation types 34 Instruction manual SGS Installation 3...
Страница 57: ...Conversion to a different gas category 54 Instruction manual SGS 4 is...
Страница 65: ...Draining 62 Instruction manual SGS 6 gis...
Страница 71: ...Status of the water heater 68 Instruction manual SGS 8 gis...
Страница 75: ...Shutting down 72 Instruction manual SGS 10 gis...
Страница 103: ...Service interval 100 Instruction manual SGS 14 is...
Страница 112: ...Instruction manual SGS 109 is...
Страница 117: ...Appendices 114 Instruction manual SGS 17 is 17 5 Declaration of conformity Declaration of conformity...
Страница 119: ...Instruction manual SGS 116...