36
Servicing should only be performed by a Qualified Service Agent
FIGURE 24. OPERATION SCREEN
FIGURE 25. FIRING RATE PAGE
HIGH FIRING RATE SETTING
Set the boiler/water heater to the high firing rate by setting the High Firing Rate RPM as described below. Check combustion readings
using a combustion analyzer. If combustion readings are not in accordance with the chart below adjust the gas valve as follows:
remove the flat, round, blue plastic cap from the cover. For more information, refer to the Instruction Manual. Using a 3 mm (7/64”)
hex wrench, turn the adjustment screw counterclockwise to increase or clockwise to decrease gas flow and achieve the desired CO
2
level. Refer to the Table 7 for correct settings. There will be a slight time delay between the adjustment and the response of the CO
2
measuring instrument. Adjust the settings in small increments and allow the combustion readings to stabilize before readjusting.
When desired adjustments are complete, reinstall the blue plastic cap on the cover. Combustion samples should be taken in the stack
within two feet of the boiler/water heater. The carbon monoxide (CO) values in the combustion sample should not exceed 150 PPM
under any circumstances. Contact OEM for any abnormal conditions leading to excessive CO above 150 PPM.
TABLE 7. HIGH FIRE RATE SETTING
MODELS (XB/XW)
RPM
(APPROXIMATE FACTORY SET)
CO
2
*MANIFOLD PRESSURE
INCHES W.C (KPA)
NATURAL
GAS
PROPANE
NATURAL
GAS
PROPANE
NATURAL GAS
PROPANE
1000
4450
4750
8.5 - 9.2%
9.3 - 10.2%
-3.5 (-0.87)
-4.7 (-1.17)
1300
4850
5100
8.5 - 9.2%
9.3 - 10.2%
-3.0 (-0.75)
-3.6 (-0.89)
1700
5700
5700
8.5 - 9.2%
9.3 - 10.2%
-3.6 (-0.89)
-4.4 (-1.09)
2000
4700
4750
8.5 - 9.2%
9.3 - 10.2%
-3.9 (0.97)
-4.9 (-1.22)
2600
5200
5100
8.5 - 9.2%
9.3 - 10.2%
-3.3 (-0.82)
-3.6 (-0.89)
3400
5700
5700
8.5 - 9.2%
9.3 - 10.2%
-3.5 (-0.87)
-4.4 (-1.09)
Содержание 100 Series
Страница 2: ...2 Servicing should only be performed by a Qualified Service Agent...
Страница 26: ...26 Servicing should only be performed by a Qualified Service Agent Figure 17 CONTROL BOARD ASSEMBLY...
Страница 34: ...34 Servicing should only be performed by a Qualified Service Agent LIGHTING AND OPERATING INSTRUCTIONS...
Страница 47: ...47 Servicing should only be performed by a Qualified Service Agent Figure 31 S7999D DISPLAY PAGE FLOW...
Страница 77: ...77 Servicing should only be performed by a Qualified Service Agent NOTES...
Страница 78: ...78 Servicing should only be performed by a Qualified Service Agent NOTES...
Страница 79: ...79 Servicing should only be performed by a Qualified Service Agent NOTES...