28
Servicing should only be performed by a Qualified Service Agent
CONNECTORS PINS
TERMINOLOGY
DESCRIPTION AND RATING
J7
1
SIPHON
Condensation Switch Input.
2
F1
Flapper Switch Input.
3
Not Used
4
SYS_ENABLE
Annunciator for System Enable Switch.
5
LGP
Annunciator for Low Gas Pressure Switch.
6
HGP
Annunciator for High Gas Pressure Switch.
7
Not Used
J8
1
SOLA1_PWR
24VAC Power Input form Terminal Block.
2
SOLA1_S_RTN
24VAC Return Input from Terminal Block.
3
Not Used
4
INLET TEMP
Supply for, and signal input from 10K or 12K Ohm NTC Inlet
Temperature sensor. Connects to Pin 2 on Inlet Temperature
Sensor.
5
INLET TEMP Common
Ground reference for the Inlet Temperature Sensor. Connects
to Pin 1 on Inlet Temperature Sensor.
6
Not Used
7
Not Used
8
OUTLET TEMP
Supply for, and signal input from 10K or 12K Ohm NTC Outlet
Temperature Sensor. Connects to Pin 2 on Outlet Temperature
Sensor.
9
OUTLET TEMP Common
Ground reference for the Outlet Temperature Sensor. Connects
to Pins 3 & 4 on Outlet Temperature Sensor.
10
OUTLET TEMP
Supply for, and signal input from 10K Ohm NTC Outlet
Temperature Sensor. Connects to Pin 1 on Outlet Temperature
Sensor.
11
Supply for, and signal input from 10K or 12K Ohm NTC
Header Sensor.
12
HEADER -
Ground reference for the Header Sensor.
J9
1
Not Used
2
Not Used
3
Not Used
4
STACK TEMP
Supply for, and signal input from 10K or 12K Ohm NTC Flue
Sensor. Connects to Pin 2 on Flue Sensor.
5
STACK Common
Ground reference for the Flue Sensor. Connects to Pin 3 & 4
on Flue Sensor.
6
STACK TEMP/Heat Exchanger
Unit)
Supply for, and signal input from 10K Ohm NTC Flue Sensor.
Connects to Pin 1 on Flue Sensor.
7
Not Used
J10
1
REMOTE RESET
Open/Ground Input that has functionality corresponding to
pushing/releasing the local reset.
2
TOD (Time of Day)
Open/Ground Input which switches operating set points.
3
TOD/REMOTE RESET COMMON
Ground reference for time of day and remote reset inputs.
4
MODULATION 4 - 20mA (+) (Out)
4 to 20 mA Current modulation signal out into a 600 Ohm.
5
MODULATION 0 - 10 VDC (+) (Out) 0 to 10 VDC Voltage modulation signal out, 10 mA max.
6
MODULATION COMMON (-)
Ground reference for voltage and current modulation signals.
7
Not Used
8
Not Used
SPECIAL CONNECTIONS
Flame +
FS +
Testpoint for Flame signal. 0 to 10
VDC
Flame -
FS -
Testpoint for Flame signal - Ground
reference.
Содержание 100 Series
Страница 2: ...2 Servicing should only be performed by a Qualified Service Agent...
Страница 26: ...26 Servicing should only be performed by a Qualified Service Agent Figure 17 CONTROL BOARD ASSEMBLY...
Страница 34: ...34 Servicing should only be performed by a Qualified Service Agent LIGHTING AND OPERATING INSTRUCTIONS...
Страница 47: ...47 Servicing should only be performed by a Qualified Service Agent Figure 31 S7999D DISPLAY PAGE FLOW...
Страница 77: ...77 Servicing should only be performed by a Qualified Service Agent NOTES...
Страница 78: ...78 Servicing should only be performed by a Qualified Service Agent NOTES...
Страница 79: ...79 Servicing should only be performed by a Qualified Service Agent NOTES...