Servicing should only be performed by a Qualified Service Agent
INSTALLATION CONSIDERATIONS
This section of the Service Manual covers some of the critical installation requirements that, when overlooked, often result in
operational problems, down time and needless parts replacement. Costs to correct installation errors are not covered under the
limited warranty. Ensure all installation requirements and instructions contained in the Instruction Manual that came with the boiler/
water heater have been followed prior to performing any service procedures.
INSTRUCTION MANUAL
Have a copy of the Instruction Manual that came with the boiler/water heater on hand for the model and series number being serviced.
Installation information given in this Service Manual is not a complete installation instruction. Installation information given in this
manual has a limited focus as it applies to servicing the boiler/water heater. This Service Manual does not replace or supersede the
Instruction Manual that came with the boiler/water heater. Always refer to the Instruction Manual for complete installation instructions.
If the Instruction Manual is not on hand copies can be obtained from the manufacturer's web site or by calling the technical support
phone number shown on the back cover of this manual.
CLOSED WATER SYSTEMS
Water supply systems may, because of code requirements or such conditions as high line pressure, among others, have installed
devices such as pressure reducing valves, check valves, and back flow preventers. Devices such as these cause the water system
to be a closed system.
THERMAL EXPANSION
As water is heated, it expands (thermal expansion). In a closed system the volume of water will grow when it is heated. As the
volume of water grows there will be a corresponding increase in water pressure due to thermal expansion. This type of failure is not
covered under the limited warranty. Thermal expansion can also cause intermittent Temperature-Pressure Relief Valve operation:
water discharged from the valve due to excessive pressure build up. This condition is not covered under the limited warranty. The
Temperature-Pressure Relief Valve is not intended for the constant relief of thermal expansion.
A properly sized thermal expansion tank must be installed on all closed systems to control the harmful effects of thermal expansion.
Contact a local plumbing service agency to have a thermal expansion tank installed.
AIR REQUIREMENTS
Carefully review the requirements for combustion and ventilation air in the Instruction Manual that came with the boiler/water heater.
Failure to meet these requirements when the boiler/water heater is installed or overlooking their importance when servicing the boiler/
water heater often results in needless down time, unnecessary parts replacement, and customer dissatisfaction.
An inadequate supply of air for combustion and ventilation often causes operational problems. A lack of combustion and ventilation air
can create a negative ambient air pressure in the installed space which can lead to improper combustion and operational problems.
CONTAMINATED AIR
Combustion air that is contaminated can greatly diminish the life span of the boiler/water heater and the components such as Igniters
and Burners. Propellants of aerosol sprays, beauty shop supplies, water softener chemicals and chemicals used in dry cleaning
processes that are present in the combustion, ventilation or ambient air can cause such damage.
Vapors from volatile compounds such as solvents, cleaners, chlorine based chemicals and refrigerants in addition to being highly
flammable in many cases, can also react to form highly corrosive substances such as hydrochloric acid inside the combustion
chamber. The results can be hazardous and cause product failure.
If the boiler/water heater is installed in beauty shops, barber shops or laundries with dry cleaning equipment, it is imperative the boiler/
water heater be installed in a Direct Vent configuration so that air for combustion is derived directly from the outdoor atmosphere
through a sealed intake air pipe. See the venting installation section in the Instruction Manual that came with the boiler/water heater
for more information on Direct Vent installations.
Содержание 100 Series
Страница 2: ...2 Servicing should only be performed by a Qualified Service Agent...
Страница 26: ...26 Servicing should only be performed by a Qualified Service Agent Figure 17 CONTROL BOARD ASSEMBLY...
Страница 34: ...34 Servicing should only be performed by a Qualified Service Agent LIGHTING AND OPERATING INSTRUCTIONS...
Страница 47: ...47 Servicing should only be performed by a Qualified Service Agent Figure 31 S7999D DISPLAY PAGE FLOW...
Страница 77: ...77 Servicing should only be performed by a Qualified Service Agent NOTES...
Страница 78: ...78 Servicing should only be performed by a Qualified Service Agent NOTES...
Страница 79: ...79 Servicing should only be performed by a Qualified Service Agent NOTES...