64
Servicing should only be performed by a Qualified Service Agent
CODE
DESCRIPTION
RECOMMENDED TROUBLESHOOTING OF
LOCKOUT CODES
NOTE
122
Lightoff rate proving failed
1.
Check wiring and correct any potential wiring
errors.
2.
Check VFDs ability to change speeds.
3.
Change the VFD.
4.
If the fault persists, replace the module.
L
123
Purge rate proving failed
L
124
High fire switch OFF
1.
Check wiring and correct any potential wiring
errors.
2.
Check High Fire Switch to assure proper function
(not welded or jumpered).
3.
Manually drive the motor to the High Fire position
and adjust the HF switch while in this position
and verify voltage through the switch to the HFS
input with a voltmeter.
4.
If steps 1-3 are correct and the fault persists,
replace the module.
H
125
High fire switch stuck ON
H
126
Low fire switch OFF
1.
Check wiring and correct any potential wiring
errors.
2.
Check Low Fire Switch to assure proper function
(not welded or jumpered).
3.
Manually drive the motor to the High Fire position
and adjust the LF switch while in this position and
verify voltage through the switch to the LFS input
with a voltmeter.
4.
If steps 1-3 are correct and the fault persists,
replace the module.
H
127
Low fire switch stuck ON
H or L
128
Fan speed failed during prepurge
1.
Check wiring and correct any potential wiring
errors.
2.
Check VFDs ability to change speeds.
3.
Change the VFD.
4.
If the fault persists, replace the module.
H or L
129
Fan speed failed during preignition
H or L
130
Fan speed failed during ignition
H or L
131
Fan movement detected during standby
H
132
Fan speed failed during run
H
133-135 RESERVED
Start Check Faults
136
Interrupted Airflow Switch failed to close
1.
Check wiring and correct any possible wiring
errors.
2.
Check Interrupted Airflow switch(es) to assure
proper function.
3.
Verify voltage through the airflow switch to the
IAS input with a voltmeter.
4.
If steps 1-3 are correct and the fault persists,
replace the module.
H
137
ILK failed to close
1.
Check wiring and correct any possible shorts.
2.
Check Interlock (ILK) switches to assure proper
function.
3.
Verify voltage through the interlock string to the
interlock input with a voltmeter.
4.
If steps 1-3 are correct and the fault persists,
replace the module.
H
138-142 RESERVED
FAULT CODES 149 THROUGH 165 ARE
OEM SPECIFIC FAULT CODES
143
Internal fault: Flame bias out of range 1
Contact the qualified service technician.
L
144
Internal fault: Flame bias out of range 2
Contact the qualified service technician.
L
145
Internal fault: Flame bias out of range 3
Contact the qualified service technician.
L
146
Internal fault: Flame bias out of range 4
Contact the qualified service technician.
L
147
Internal fault: Flame bias out of range 5
Contact the qualified service technician.
L
148
Internal fault: Flame bias out of range 6
Contact the qualified service technician.
L
Содержание 100 Series
Страница 2: ...2 Servicing should only be performed by a Qualified Service Agent...
Страница 26: ...26 Servicing should only be performed by a Qualified Service Agent Figure 17 CONTROL BOARD ASSEMBLY...
Страница 34: ...34 Servicing should only be performed by a Qualified Service Agent LIGHTING AND OPERATING INSTRUCTIONS...
Страница 47: ...47 Servicing should only be performed by a Qualified Service Agent Figure 31 S7999D DISPLAY PAGE FLOW...
Страница 77: ...77 Servicing should only be performed by a Qualified Service Agent NOTES...
Страница 78: ...78 Servicing should only be performed by a Qualified Service Agent NOTES...
Страница 79: ...79 Servicing should only be performed by a Qualified Service Agent NOTES...