27
Servicing should only be performed by a Qualified Service Agent
CONNECTORS PINS
TERMINOLOGY
DESCRIPTION AND RATING
J1
1
Not Used
2
FLAME SENSE1/2: SENSE
Flame Rod Input.
3
FLAME SENSE1/2: GND
Flame Rod Common.
4
Not Used
5
Not Used
6
Not Used
J2
1
TACH
Tachometer Input (Tach).
2
25VDC
Electronic Blower Motor Power (25 VDC).
3
PWM
Digital modulation (PWM) Output Digital modulation signal out.
4
GND
Ground pin for Fan interface and power.
J3
MB1
A
Modbus MB1 RS-485 +. Connects to Display.
B
Modbus MB1 RS-485 -. Connects to Display.
C
Modbus MB1 Ground (G). Connects to Display.
MB2
A
Modbus MB2 RS-485 +. Connects to Local Burner Control
Board for Lead lag application.
B
Modbus MB2 RS-485 -. Connects to Local Burner Control
Board for Lead lag application.
C
Modbus MB2 RS-485 Ground (G). Connects to Local Burner
Control Board for Lead lag application.
ECOM
1: Not Used
2: Not Used
3: Not Used
J4
1
Not Used
2
Not Used
3
Not Used
4
Not Used
5
Not Used
6
PUMP1/PUMP Output
120 VAC Power output to Pump Relay.
7
H_PUMP/PUMP Input
120 VAC Power input from Power Distribution Block.
8
Not Used
9
Not Used
10
SOLA1_L_RTN
120 VAC Power Supply Neutral.
11
Not Used
12
G/EARTH GROUND
Earth Ground.
J5
1
INTERLOCK/BFS
Blocked Flue Switch. Per Model Input Rating.
2
GV1
24VAC Power input to the Gas Valve.
3
Not Used
4
Not Used
5
Not Used
6
SPARK_G1
120 VAC Power output to Spark Generator.
7
H_BLOW_SPRK
120 VAC Power input from Power Distribution Block.
J6
1
LWCO
Annunciator for LWCO Input.
2
Not Used
3
FLOW_SW
Annunciator for Flow Switch Input.
4
Not Used
5
Not Used
6
Not Used
7
Not Used
8
Not Used
TABLE 3. CONTROL BOARD CONTACTS/CONNECTIONS
Содержание 100 Series
Страница 2: ...2 Servicing should only be performed by a Qualified Service Agent...
Страница 26: ...26 Servicing should only be performed by a Qualified Service Agent Figure 17 CONTROL BOARD ASSEMBLY...
Страница 34: ...34 Servicing should only be performed by a Qualified Service Agent LIGHTING AND OPERATING INSTRUCTIONS...
Страница 47: ...47 Servicing should only be performed by a Qualified Service Agent Figure 31 S7999D DISPLAY PAGE FLOW...
Страница 77: ...77 Servicing should only be performed by a Qualified Service Agent NOTES...
Страница 78: ...78 Servicing should only be performed by a Qualified Service Agent NOTES...
Страница 79: ...79 Servicing should only be performed by a Qualified Service Agent NOTES...