63
Servicing should only be performed by a Qualified Service Agent
CODE
DESCRIPTION
RECOMMENDED TROUBLESHOOTING OF
LOCKOUT CODES
NOTE
94
Header sensor fault
1.
Check wiring and correct any possible errors.
2.
Replace the header sensor.
3.
If previous steps are correct and fault persists,
replace the module.
H
95
Stack sensor fault
1.
Check wiring and correct any possible errors.
2.
Replace the stack sensor.
3.
If previous steps are correct and fault persists,
replace the module.
H
96
Outdoor sensor fault
1.
Check wiring and correct any possible errors.
2.
Replace the outdoor sensor.
3.
If previous steps are correct and fault persists,
replace the module.
H
97
Internal Fault: A2D mismatch
Internal Fault.
1.
Reset Module.
2.
If fault repeats, replace module.
L
98
Internal Fault: Exceeded VSNSR voltage
L
99
Internal Fault: Exceeded 28V voltage tolerance
L
100
Pressure Sensor Fault
1.
Verify the Pressure Sensor is a 4-20ma source.
2.
Check wiring and correct any possible errors.
3.
Test Pressure Sensor for correct operation.
4.
Replace the Pressure sensor.
5.
If previous steps are correct and fault persists,
replace the module.
H
101-104 RESERVED
Flame Operation Faults
105
Flame detected out of sequence
1.
Check that flame is not present in the combustion
chamber. Correct any errors.
2.
Make sure that the flame detector is wired to the
correct terminal.
3.
Make sure the F & G wires are protected from
stray noise pickup.
4.
Reset and sequence the module, if code
reappears, replace the flame detector.
5.
Reset and sequence the module, if code
reappears, replace the module.
H or L
106
Flame lost in MFEP
1.
Check pilot valve (Main Valve for DSI) wiring and
operation - correct any errors.
2.
Check the fuel supply.
3.
Check fuel pressure and repeat turndown tests.
4.
Check ignition transformer electrode, flame
detector, flame detector siting or flame rod
position.
5.
If steps 1 through 4 are correct and the fault
persists, replace the module.
L
107
Flame lost early in run
L
108
Flame lost in run
L
109
Ignition failed
L
110
Ignition failure occurred
Hold time of recycle and hold option. Will not be a
lockout fault. Hold Only.
H
111
Flame current lower than WEAK threshold
Internal hardware test. Not a lockout.
H
112
Pilot test flame timeout
Interrupted Pilot or DSI application and flame lost
when system in “test” mode.
1. Reset the module to restart.
L
113
Flame circuit timeout
Flame sensed during Initiate or off cycle, hold 240
seconds, if present after 240 seconds, lockout.
L
114-116
RESERVED
117
Condensate Fault
1.
Check the condensate trap at the back of the
boiler/water heater for any blockage.
2.
Check the exhaust vent piping for any blockage.
L
118-121
RESERVED
Rate Proving Faults
Содержание 100 Series
Страница 2: ...2 Servicing should only be performed by a Qualified Service Agent...
Страница 26: ...26 Servicing should only be performed by a Qualified Service Agent Figure 17 CONTROL BOARD ASSEMBLY...
Страница 34: ...34 Servicing should only be performed by a Qualified Service Agent LIGHTING AND OPERATING INSTRUCTIONS...
Страница 47: ...47 Servicing should only be performed by a Qualified Service Agent Figure 31 S7999D DISPLAY PAGE FLOW...
Страница 77: ...77 Servicing should only be performed by a Qualified Service Agent NOTES...
Страница 78: ...78 Servicing should only be performed by a Qualified Service Agent NOTES...
Страница 79: ...79 Servicing should only be performed by a Qualified Service Agent NOTES...