Manual WS.502 v1.5
2-Wire Energy Monitor
2
Characteristics WS.502:
1.
DIN-rail module (2 modules wide)
2.
Power supply: 15V/1A
3.
Bus connection: MODBUS (max. 32 modules)
4.
RF LORA-FSK transceiver 868 MHz, 100mW
5.
Ethernet connection with integrated transfo's
6.
Network processor 10/100Mbit/sec
7.
Real Time Clock with backup battery synced
daily with NTP server
8.
FRAM memory for backup meter readings 32
kb
9.
SD card 8Gb (backup configuration and
datalogs 3 years)
10.
Upgrading via FTP-server 2-WIRE
11.
64 log channels, each up to 5 readings (32bits)
and 2 consumption values (import export)
12.
Communication every minute to the
connected modules for the readings
13.
Logging every minute to SD of 5
measurements per channel, every 5 minutes
for consumption
14.
Use costings with adjustable period
(approximate, NOT FOR OFFSET)
15.
EPC level calculation (kWh/m2)
16.
Web server HTML : 4 users + 1 administrator
can use the server simultaneously.
17.
Login, password and language choice (NL-FR-
EN-DU) per user.
18.
IP-adres fix of dynamisch via DHCP-server
19.
Domain name instead of IP address possible
via DNS server
20.
Full configuration of all modules, creating
groups for layout
21.
FTP Client: Set rhythm for logging data to
remote FTP server individually adjustable for
real-time measurements (interval per minute,
up to 60 minutes) and for consumption
measurements (interval per 5min, up to 24h).
The format is CSV, in the AMR-MMR format
(BE: EANDIS). Each file has a unique name and
can be processed in your own database.
22.
Exporting data to a local csv file
23.
Deactivated for MEMo2 (
HTTP-request: Via a
instruction set all readings and consume
requests per channel, from a chosen time and
a certain period (1 day to 31 days). The format
is JSON and can easily be converted to tables.
)
24.
Deactivated for MEMo2
Online operation or
request statuses of vb relay contacts,
thermostat can also be via an HTTP request.
25.
Visual logic user interface for monitoring or
controlling consumer, creating calculated
graphs,...
1.
BUS STRUCTURE
The WS.502 has 2 communicationsystems on board:
a wirelessRFbus according to the LORAprotocol, and a
MODBUScommunication.
1.
MODBUS:
GND = BUSCLAMP 1
,
A =
BUSCLAMP 2, B = BUSCLAMP 3
2.
EC.441-RG.016:
GND = BUSCLAMP 1, A =
BUSCLAMP 2, B = BUSCLAMP 3, VDD =
BUSCLAMP 4
Between the clamps A-B, the supplied resistors (120
ohm) must be placed on both ends of the bus!
Recommended is EIB bus cable (4 wire)
More info: please consult documentation modules
3.
Start
1.
Supplied power supply (15V) to WS.502
connect to power clamps at the top. (Polarity
does not play a role)
2.
Connect network cable at the bottom must be
connected to the Internet via switch or
(wireless) router.
3.
Connect bus to the energy modules: EC.441
–
RG.016
–
EMMxxx etc.
4.
Attention:
Always connect first network cable
and only then provide power to the Memo
server
Power supply: at the top of the WS.502,all LEDs must
be lit. After a few seconds, led L2 should go out,
followed by LED L3 and LED L4. Afterwards, led L3 will
light up every 2 seconds (heart-beat)