3.1 Putting in Operation
Operational state is
's main function. In this state, periodic data
2N SmartCOM
®
readouts from input circuits are made.
responds to queries from the
2N SmartCOM
®
superior data concentrator, which can be the
server, monitors the
2N
SmartCOM
®
events on the RS-232 / 485 / M-Bus interfaces and sends the acquired data to the
server via GPRS, or Ethernet in the case of the PRO ETH version.
Initialisation
Insert the PIN–disabled data SIM card in
and connect the GSM
2N SmartCOM
®
antenna and power supply as instructed in
., Mounting.
Subs. 2.3
When the
power supply is connected, the LED indicator on the upper
2N SmartCOM
®
side of the module flashes three times quickly and then starts flashing in longer
intervals. Refer to
. for LED status details. The GPRS module starts
Subs. 3.2
communicating with the provider in about 10 seconds trying to log in and obtain the IP
address. The LED starts shining constantly to indicate a successful login.
Tip
2N SmartCOM
®
is working if the LED indicator is shining, thus
indicating a successful mobile provider connection and IP address
assignment.
To identify the
IP address assigned by the mobile provider or perform
2N SmartCOM
®
the basic configuration upon power up, get connected via the serial port (RS 232). The
port is in the data mode upon power up, retransmitting all data from the input to the
GPRS network. Use the +++ sequence preceded and followed by a 1–second delay to
switch into the configuration mode. When your
replies OK, start
2N SmartCOM
®
configuring using the AT commands as listed below.
Restart the serial port to return to the data mode. To do so, you can either send the
ATO command or disconnect
from the power supply.
2N SmartCOM
®
Tip
can also be configured via Terminal Config. Refer to
2N SmartCOM
®
.
S. 6
If you cannot use a PC, make the basic settings using SMS messages.
Refer to
for details.
S. 5
When your
has been programmed as required, connect the device to
2N SmartCOM
®
the available serial ports RS-232 / 485 / M-Bus. Launch the hyperterminal and get
connected to the
public IP address via port 10000, which, together
2N SmartCOM
®
with the serial port, can be used for configuring. Use port 10001 for retransmitting data
to RS-232 and port 10002 for retransmitting data to RS-485 / M-Bus.