ZDAS-16CA SERIES PROGRAMMING GUIDE
--------------------------------------------------------------------------------------------------------------------------------------------------------
PAGE
12
OF 19
for 1 second.
Note: JP1 jumper on the main board must be short connected before this operation.
4.3 Change user Password
1.Change Primary password: Primary password (6 bit) + 08 +
(Confirm Key), the setting
indicator LED on, input new primary password (6 bit) +
(Confirm Key), after the buzzer sound
a long “Di”, the indicator LED light off, new primary password is in effect. (Factory default Primary
password: 123456)
2. Add Subsidiary Password: Primary password (6 bit) + 08 +
(Confirm Key), the setting
indicator LED on, input subsidiary password number (2 bit) +
(Confirm Key),(01-15 means the
serial number of 15 groups subsidiary password) the corresponding LED light on. Input subsidiary
password (4 bit) +
(Confirm Key), after the buzzer sounds a long “Di”, new subsidiary
password is in effect.
3. Delete subsidiary password: Primary password (6 bit) + 08 +
+ subsidiary password
serial
+
, the buzzer will give a long “di” if deleting succeed
。
4
.
*# Exit setting status
,
or exit automatically after 30 seconds
Note
:
:
:
:
Subsidiary password can be used disarm for Away ARM, Fast Arm, Boundary ARM and
Compelled ARM.
4.4 Start & Exit Set Mode
1. Start Set Mode:
Operation: Installer password (6 bit) +
(Confirm Key) (Factory Installer Password: 666666)
Status: If set successfully, the buzzer will sound a long ”Di”; the Indicator LED will light on; If failed,
the buzzer will sound 3 shot “Di”.
2
.
.
.
.
Exit Set Mode:
Operation: * #
,
Or exit automatically after 30 seconds
Status: If Exit set status successfully; the buzzer will sound a long “Di”, the indicator LED will light off;
Or exit automatically after 30 seconds, the buzzer will not sound, indicator LED off.
Note: All operations for the following step(4.5-4.39) must be carried out under Set Mode
status(please exit set mode if need normal operation).
4.5 Change Installer Password
Format: 30
+
New Installer Password (6 bit)
+
(Confirm Key);
4.6 Learn Wireless Detectors
(only for ZDAS-16CA-8/16/16G)
1.Format: 20
+
zone number (2 bit)
+
(Confirm Key), Zone number is from 01~16.
Corresponding zone LED will light on.
2. Learning Code: Press any button of remote controller or trigger the detector to send wireless
signal to alarm panel. The signal LED will light up when the alarm panel received the signal, Press
(Confirm Key), the corresponding zone LED light off, means the panel’s memory already saved
the wireless address code to specified zone, then the panel will receive, and identify the
corresponding wireless signal address, and give alarm once detector is triggered.
4.7 Delete Wireless Detectors
(only for ZDAS-16CA-8/16/16G)
Format: 21
+
zone number (2 bit)
+
(Confirm Key); Zone number is from 01~16.
Note: If the deleted detectors activated, the LED indicator on keypad will not light on.
4.8 Set Zone Type and Siren Output
1. Operation: Zone number (2 bit)
+
Zone type (1 bit)
+
Siren status (1 bit)
+
(Confirm
Key);
Zone number: 01
~
16, indicates 1
~
~
~
~
16 zone.
Zone Type: 0 Instant zone; 1 Fire Zone; 2 Emergency Zone; 3 Delay zone; 4 24 Hours zone; 5
Anti-Tamper Zone (alarm while the zone is triggered at least 2 times in 30
seconds); 6 Gas Zone; 7 BY-PASS zone, 8 Access Zone (System will under