30/71
User Manual for hybrid inverter HYD 10-20KTL-3PH - Rev. 1.0 of 25/08/2020
Identification: MD-AL-GI-00
Identification: MD-AL-GI-00
Rev. 4.0 of 31.01.18 - Application: GID
7
NC
Not connected
Not connected
8
NC
Not connected
Not connected
Table 8 – Terminal description
Table 9 – Inverter preconfigured for the RRCR power levels (1 closed, 0 open)
No.
PIN name
Description
Connected to (RRCR)
1
L1
Input contact relay 1
K1 – Output relay 1
2
NC
Not connected
Not connected
3
NC
Not connected
Not connected
4
NC
Not connected
Not connected
5
NC
Not connected
Not connected
6
G
GND
K1 – Output relay 1
7
NC
Not connected
Not connected
8
NC
Not connected
Not connected
Table 10- Terminal description
L1
Active Power
Power drop rate
Cos(φ)
1
0%
< 5 seconds
1
0
100%
/
1
Table 11 - Inverter preconfigured for the RRCR power levels (1 closed, 0 open)
L1
L2
L3
L4
Active power
Cos(φ)
1
0
0
0
0%
1
0
1
0
0
30%
1
0
0
1
0
60%
1
0
0
0
1
100%