23/71
User Manual for hybrid inverter HYD 10-20KTL-3PH - Rev. 1.0 of 25/08/2020
Identification: MD-AL-GI-00
Identification: MD-AL-GI-00
Rev. 4.0 of 31.01.18 - Application: GID
using the hex key.
NB:
L3 is the length between the insulating layer of the ground cable, the L4 curved part and
the core wires protruding from the secured part.
NB:
The cavity formed on the conductor just below the crimping strip must completely wrap
the core wires, which must be in contact with the terminal.
Figure 13 - Installation of crimped terminal
4.2.
Connecting the battery
Before removing the positive and negative connectors, make sure that the DC
circuit breaker is open.
Danger
Procedure:
1.
Select the type of cable with the appropriate specifications according to Table 6. Remove the
cable glands from the positive and negative connectors (it is recommended to distinguish the
positive and negative with different colours).
2.
Remove an appropriate length of the insulating layer from the negative and positive power
cables using a wire stripper
Figure 14 - Removal of insulating layer
1)
M5 screw
2)
OT Terminal
3)
Threaded hole
1)
Positive metal
contact
2)
Negative metal
contact