Chapter 9
Signal Cable Installation
Install signal cables among physical entities, so that control and data signals can be
transmitted among these entities.
Obtain the specific wiring table as required.
Table of Contents
9.1 Signal Cable Installation Requirements
Cabling Principles
l
Before installation, signal cables must pass the continuity test. Both sides of each
signal cable should be marked or labeled correctly.
l
Signal cables must be free of damage, breakage, and joints.
l
Do not route signal cables on ventilation holes because this will affect heat dissipation
and cable life.
l
During the cabling, it is not allowed to bind power cables and signal cables together.
l
Cabling in the cabinet must not affect door installation.
l
Cables must be routed along the horizontal and vertical cable trays in a flat and straight
manner, without crossovers or folds.
l
For a small number of optical fibers, the fibers can be routed together with other cables
and protected in soft management sets. For a great number of optical fibers, the fibers
should be routed along vertical cable trays and protected in sylphon bellows.
Binding Principles
l
Cables should be bound with appropriate force and tightened properly. Cable ties
should be arranged in the same direction.
l
The surplus part of the cable tie should be cut off from the root without any jagged
edge.
l
Take protective measures when attaching a signal cable to a sharp structural
component.
l
Optical fibers should be bound with the optical fiber ties for protection.
9-1
SJ-20141121113158-006|2014-12-20 (R1.0)
ZTE Proprietary and Confidential