Setting actuator by means of push-buttons:
– Shift the change-over switch of local control to position OFF
– Keep pressing push-button STOP to enter the MENU. Using push-buttons O or Z, browse through the MENU
(MENU1 – MENU27).
Shortly press push-button STOP in a selected menu to enter this menu and, using push-
buttons O or Z, select the parameter. Keep pressing push-button STOP to store the parameter to memory. Shortly
press push-button STOP to exit the setting of parameters and proceed with browsing through another menu.
Keep pressing push-button STOP to exit the set menu; or keep pressing push-button STOP in the item END after
the last MENU 27 to terminate the setting regime.
Setting end-limit positions by means of push-buttons of local control
Shift the change-over switch LOCAL – REMOTE to position OFF. Keep pressing push-button STOP to enter the
setting regime. Using push-button “Z”, choose MENU2. Shortly press push-button STOP to select setting of position
“O”. Shift the change-over switch to position “LOCAL” and start the actuator. After the required position is reached, shift
the switch to position “OFF” and keep pressing of push-button “STOP” to store the position to memory.
Shortly press push-button “Z” to select setting of position “Z”. Shift the change-over switch again to position “LOCAL”
and start the actuator in direction “Z”. After the required position is reached, shift the switch to position “OFF” and keep
pressing push-button “STOP” to store the position to memory.
Shortly press push-button “STOP” to exit MENU 2. Keep pressing push-button “STOP” to exit the setting regime.
Change over the local control to position OFF, enter the menu
(by long pressing of push-button STOP),
and change
over to position “LOCAL”; the actuator can now be shifted by means of push-buttons “O” and “Z” beyond the set end-li-
mit positions. In this case, the actuator will trip after the set tripping torque is reached.
Autocalibration
In the setting regime choose MENU 3. Shortly press push-button “STOP” to enter MENU 3 and keep pressing
push-button “STOP” to start autocalibration. By short starting of the motor in both directions, the actuator will measure
inertia. Completion of the autocalibration is announced by the message AUTOCALIBRATION OK.
Shortly press push-button “STOP” to return to MENU 3 and keep pressing of push-button “STOP” to exit the setting
regime.