12
Setting program
The setting program is same for communication with the electronics
DMS2ED and DMS2. The users'
version can be freely downloaded.
Note: In the window “Parameters” of the setting program, column “Access”, the word “NO” designates parameters
that cannot be changed by the user (change of these parameters is blocked).
PROCEDURE OF SETTING PARAMETERS BY MEANS OF PUSH-BUTTONS
For simple programming of required operating parameters, the control unit is fitted with four push-buttons:
MENU, P, O, C and three signal lamps.
Yellow
Red
Green
State
-
-
-
System without feeding
-
-
lit on
Everything OK – working regime
(remote, local or switched off control)
-
blinking
lit on
Error or warning – working regime
(remote, local or switched off control)
lit on
-
lit on
Enter or exit of Setting of parameters by means of push-buttons
or Setting of parameters by means of PC
blinking
-
lit on
blinking blinking
lit on
Setting of parameters by means of push-buttons
blinking blinking
lit on
In adjustment, follow the paragraphs “VERIFICATION of APPARATUS FUNCTION And its LOCATION”,
“fitting on VALVE” and “ADJUSTMENT of ACTUATOR with VALVE” of these instructions.
For safety reasons, the system is delivered in the state of induced error of Calibration when the functions are
limited in order to reduce the risk of damage to the actuator by wrong wiring.
Record of position CLOSED, OPEN and AUTOCALIBRATION
– The actuator must be adjusted in such a way that the recorded position would switch off the actuator before it
is switched off by torque. For tight closure, the torque relay for torque Closed is only connected into the control
circuit. The actuator can be shifted either manually or electrically. The actuator in version CONTROL can be
started from menu MOTOR in program DMS2. In this case, the actuator does not react to the set position
and can only be stopped by the torque relay. In controlling from menu MOTOR, no torque may be induced.
The torque must be left manually.
Parametr – Parametres
Změna – Change
Chyba – Fault
Přístup – Access
Setrvačnost (0,1 %) – Inertia [0.1 %]
Setr. Doběh (0,1 s) – Inertia deceleration [0.1 s]
Necitlivost (%) – Insensitivity [%]
NE – NO
COM
POWER
TORK
AIN
LED1 LED2 LED3
MENU
P
O
C
Colours of diodes:
LED1 – yellow
(menu number)
LED2 – red
(parameter value)
LED3 – green
Push-buttons and signal lamps LED on control unit DMS2.ED.S and DMS2.ED.S90