30
BQ 1
resistive transmitter
SQFC1
torque switch "open"
(MO)
SQFT1
torque switch "closed"
(MZ)
SQC1
position switch "open"
(PO)
SQT1
position switch "closed"
(PZ)
TH
thermocontact
Signals of connectors of the ZP2RE6 regulator:
Connect J1
Control signal 4 – 20 mA
position 4-20 mA
J1.1
(-IN)
terminal 35
control signal -
J1.2
(+IN)
terminal 36
control
J1.3
(COM)
terminal 50
output active position 4 – 20 mA
J1.4
(-L)
terminal 51
output position common
J1.5
(+L)
terminal 52
output possition passive 4 – 20 mA
Connect J2
Input of resistive,
or current position sensor
J2.1
(+24V)
-
J2.2
(+5V)
R sensor
J2.3
(IN)
R sensor
J2.4
(GND)
R sensor
Connect J3
Input torque and position
switches of position sensor
J3.1
(LO)
position "open"
(PO)
J3.2
(PO)
common PO – MO
J3.3
(MO)
torque "open"
(MO)
J3.4
(LZ)
position "closed"
(PZ)
J3.5
(PZ)
common PZ – MZ
J3.6
(MO)
torque "open"
(MO)
Connect J4
Block of local control
J4.1
(+24 V)
control phase
J4.2
(D)
phase for remote
(regulator function)
J4.3
(LZ)
phase for locally close
J4.4
(LO)
phase for locally open
Connect J5
Software-adjustable signal relays:
J5.1
(REM)
terminal 13
Relay 1 output for ex. Remote control
J5.2
(CL)
terminal 12
Relay output 2 for example Closed position
J5.3
(OP)
terminal 11
Relay output 3 for example Open position
J5.4
(COM)
terminal 10
linked relay 1, 2, 3 contct
Connect J6
Central fault relay:
J6.1
(NO)
terminal 16 of switching contact
J6.2
(COM)
terminal 15 common contact
J6.3
(NC)
terminal 14 break contact
Connect J7
Brake control
Connect J8
Power supply
J8.1
(9 V)
power supply 9 V
J8.2
(9 V)
power supply 9 V
J8.3
(18 V)
power supply 18 V
J8.4
(18 V)
power supply 18 V
Connect J9
Thermal fuse
J9.1
(TP230)
input 230 V
J9.2
(TP 24)
24 V input
J9.3
(TP 0)
common input
KEY TO SCHEMES