27
temperature dependence
(ČSN IEC 770)
< 0.008 % / 1 V
influence of load resistance
< 0.003 % / 100
Ω
supply voltage
12 to 30 VDC (
reverse polarity protection)
maximum value of load
resistance in current loop at Vs = 24 V DC
600
Ω
max. resistance of supply conductors to resistance transmitter
1 000
Ω
input signal
4 to 20 mA
current at break of resistance transmitter
max. 30 mA
Measuring ranges
5 to 105
Ω
0 to 130
Ω
0 to 214
Ω
0 to 500
Ω
0 to 1000
Ω
0 to 2500
Ω
0 to 5000
Ω
Device operating conditions
ambient temperature
0 to +70 °C
(-40 to +85 °C)
relative humidity
40 to 70 %
atmospheric pressure
84 to107 kPa
protection
IP 20
permissible conductor cross section
0.35 to 4 mm
2
module width
22.5 mm
box material
NORYL
box resistance to temperature
dimensional stability up to +120 ° C
box resistance to fire
flame retardant plastic
resistance and stability against vibration
10 to 60 Hz
0.14 mm
(amplitude)
60 to 500 Hz
19.6 m/s
2
(peak acceleration)
Interference resistance
ČSN IEC 801-3, Level 3
(Chapter 5)
ČSN IEC 801-4, Level 4
(Chapter 5)
ČSN IEC 801-6, Level 2
(Table 1, art. 5.1)
How to Order
The order must state the following:
number of pieces
name
order part number in the table
Sample order:
6 converters, MODEL 222-224 RIP
ord. no.: 222-224 RI P 5 to 105
Ω
Source
of power
supply
Range
Zero
Out