English - 4
© 2021 ZES - All rights reserved
IB v3.0.0 2021
GROUND CONNECTION WARNINGS
•
Charging station must be connected to a centrally grounded system. The ground conductor
entering the charging station must be connected to the equipment grounding lug inside the
charger. This should be run with circuit conductors and connected to the equipment grounding
bar or lead on the charging station. Connections to the charging station are the responsibility
of the installer and purchaser.
•
To reduce the risk of electrical shock, connect only to properly grounded outlets.
•
WARNING : Make sure that during installing and using, the charging station is constantly
and properly grounded.
POWER CABLES, PLUGS and CHARGING CABLE WARNINGS
•
Be sure that plugs and sockets are compatible on charging station side.
•
A damaged charging cable can cause fire or give you an electric shock. Do not use this product
if the flexible Charging cable or vehicle cable is frayed, has broken insulation, or shows any
other signs of damage.
•
Ensure that the charge cable is well positioned thus; it will not be stepped on, tripped over,
or subjected to damage or stress.
•
Do not forcefully pull the charge cable or damage it with sharp objects.
•
Never touch the power cable/plug or vehicle cable with wet hands as this could cause a short
circuit or electric shock.
•
To avoid a risk of fire or electric shock, do not use this device with an extension cable. If the
mains cable or vehicle cable is damaged it must be replaced by the manufacturer, its service
agent, or similarly qualified persons in order to avoid a hazard.
•
Use appropriate protection when connecting to the main power distribution cable.
•
The charging station is permanently connected.
REQUIRED UPSTREAM PROTECTIONS
•
Class-I/B Lightning Protection must be connected to the upstream distribution panel. The
charger contains Class II/C Type Surge Protector Device (SPD)
•
MCCB (Thermic Magnetic Adjustable) must be connected to the upstream distribution box.
Model
AC Sock
et1
AC Sock
et2
Schuk
o Sock
et1
Schuk
o Sock
et2
Po
w
er Output
Input Max A
C
Curr
ent
Rec
ommended
Cr
os
s Section
for A
C Mains
Requir
ed
Cir
cuit Br
eak
er
EVC05-AC44
22
22
NA
NA
44 kW
64A
25-35
mm2
80A Curve-C
EVC05-
AC44*****S*
22
22
3,7
3,7
51,4 kW
80A
25-35
mm2
100A Curve-C