XPLC300 Motion Controller Hardware Manual V1.5
“ZBasic Programming Manual” for details
.
(5)
According to their respectively instructions, correctly set the relevant parameters of
the third-party equipment to match the parameters of each node.
(6)
Correctly set the "address" and "speed" of the slave station expansion module
according to the manual of the slave station.
(7)
After all the settings are completed, restart the power supply of all stations to
establish communication.
3.1.4.
Digital Input Specification & Wiring
→
Specification
Item
General input (IN0)
Input mode
NPN leakage, input is triggered when it is low-electric level
Frequency
<
5kHz
Impedance
4.7K
Ω
Voltage level
DC24V
The voltage to open
<14.5V
The voltage to close
>14.7V
Minimal current
-1.8mA (negative)
Summary of Contents for XPLC300