The following events can be seen locally or remotely. The following list indicates the messages for the different
events both locally and remotely
Code
Display
Remoto
Level
Condition
00
System start
Minor
01
Password changed
Minor
Level password change
10
Insulation Fault 1
Minor Insulation Failure
Minor
Value RAislamiento < RAis1
with 5% hysteresis
11
Chopper HighTemp
Chopper High Temperature
Minor
Chopper temp.> TChopMax with
10% hysteresis
12
Inv. High Temp
Inverter High Temperature
Minor
Rectifier temp.> TRecMax with
10% hysteresis
13
Cabinet High Temp
Cabinet High Temperature
Serious
Cabinet temp.> TArmMax with
10% hysteresis
14
Fan Failure
Fan Failure
Minor
2 degree temperature gradient
15
Measure Com. Err.
Measures Communication
Failure
Minor
Event CComCInt
Communications failure with
the Capture Card
17
DC Measure Cont.
DC Measure Contactor
Error
Minor
Came general switch close and no
DC measurement contactor or
vice versa
18
DC OverV. Prot.
DC Overvoltage Protection
Minor
DC overvoltage protection failure
19
AC Overvoltage Protection
AC Overvoltage Protection
Minor
AC overvoltage protection failure
30
External Alarm
External Alarm
Persis.
External alarm trip
40
Insulation Fault 2
Minor Insulation Failure
Serious
Value RAislamiento < RAis2
with 5% hysteresis
41
Thermostat
Thermostat Trigger
Serious
Event FTermos
Radiator
thermostat trip
42
T. Alta Transfor
Transformer High
Temperature
Serious
Cabinet temperature> Maximum
transformer temperature 5%
hysteresis
43
DC Contactor
DC Contactor Failure
Serious
System in operation and DC
contactor input open or vice versa
44
DSP Comm. Error
DSP Communication
Failure
Serious
Event CComDSP
Communications failure with
DSP
45
Driver Failure
Driver Failure
Serious
Event Fdriver
IGBT driver
trip.
48
DC Overvoltage
DC Overvoltage
Serious
Photovoltaic voltage> VpvMax
with 5% hysteresis
49
AC overvoltage
AC Overvoltage
Serious
Event FVRedMax
AC voltage
value over defined value.
50
AC undervoltage
AC Undervoltage
Serious Events FVRedMin and not FPLL
51
Islanding
Islanding
Serious
Events FPLL y FVRedMin
Sink and is in failure with
network and AC voltage value
lower than defined value
52
AC Freq. Err.
AC Grid Frequency Error
Serious
Events FPLL, ContAC and not
FVRedMin