5.6 Relay outputs
“
K1
”
The relay output
“
K1
”
can have different functions assigned to it, see IO SETUP. Max.
contact rating see technical data and connection diagram.
Function fault indication (factory setting) for
“
K1
”
:
•
For operation the relay is energized, connections
“
13
”
and
“
14
”
are bridged. For fault
the relay is de-energized.
•
When switching off via enable (see IO SETUP/Digital inputs "DI"), the relay remains
energized.
5.7 RS-485 interface for MODBUS
The device comes equipped with a RS-485 interface for networking via MODBUS.
Conntection at:
“
A (D+)
”
,
“
B (D-)
”
and
“
GND
”
.
11.03.2014
v_am_modbus_connect.vsd
ID1
GND
A
(D+)
B
(D-)
ID2
GND
A
(D+)
B
(D-)
B
(D-)
ID1
GND
A
(D+)
B
(D-)
ID2
GND
A
(D+)
MODBUS
(RS-485)
MODBUS
(RS-485)
A
d
d
re
s
s
in
g
A
d
d
re
s
s
in
g
MODBUS
(RS-485)
MODBUS
(RS-485)
A
d
d
re
s
s
in
g
A
d
d
re
s
s
in
g
The connections for MODBUS
“
A (D+)
”
,
“
B (D-)
”
are available double on the module and are
connected with each other internally.
Information
•
You must ensure correct connection; i.e.
“
A (D+)
”
must also be connected on the
following devices to
“
A (D+)
”
. The same applies to
“
B (D-)
”
.
•
In addition, a "GND" connection must be established, as dissimilar potential (over 10
V!) will lead to the destruction of the RS-485 interface (e.g. lightning).
•
Except the data link
“
A (D+)
”
,
“
B (D-)
”
and
“
GND
”
(for automatic addressing additional
“
ID1
”
-
“
ID2
”
see following chapter) no further cable cores of the data line may be used.
•
Pay attention to suf
fi
cient distance from powerlines and motor wires (min. 20 cm).
•
A maximum of 64 participants can be directly connected to one another, and another
64 participants via a repeater.
Operating Instructions
UNIcon
CTG-150AVC
Electrical installation
L-BAL-E287-GB 2015 Index 004