8.4.3 Digital output
“
DO
”
Menu overview
Function
Designation
Fault indic. 2K
DO1 Function
Setting of the desired function (see following table).
K1
DO1 Signal
Relay output K1 (terminals: 13, 14)
No further assignment possible, n.a. (no assignment) = No signal assigned.
OFF
DO1 Inverting
Inverting output
Setting of the desired function
Function K1
Designation
OFF
No function
Relays remain always de-energized.
Operation indic.
1K
Operating message (for
2.03
not possible)
Reports a failure and switch-off using the enable function (see digital inputs
“
DI
”
).
Fault indic.
2K
Fault indication (factory setting for
2.00
+
2.01
, for
2.03
not possible)
Reports a failure, switch-off using the enable function (see digital inputs
“
DI
”
)
is not reported.
Extern. Error.
3K
Report of an external failure triggered by digital output (no function in
2.00
and
2.03
).
Limit modu.
4K
Limit message modulation (for
2.03
not possible)
Limit temp
5K
Limit message actual temperature (only for
2.01
).
Heating
9K
Heating function (only for two-position controller
2.03
)
Operating point: temperature = se/- Offset
Release point: Temperature around hysteresis over operating point