Information
Always set the value for "Temp max." higher than the value for "Temp min.".
Examples for limit messages temperature
50 %
Analog IN
0
1
100 %
1
11.05.2007
v_grenzwert_signal_k1_1.vsd
Settings
- Temp. Max.: 80
°
C
- Temp. Min.: OFF
- switching hysteresis 5 % (from
100 %)
50 %
Analog IN
0
1
100 %
2
11.05.2007
v_grenzwert_signal_k1_2.vsd
Settings
- Temp. Min.: 20
°
C
- Temp. Max.: OFF
- switching hysteresis 5 % (from
100 %)
50 %
Analog IN
0
1
100 %
3
11.05.2007
v_grenzwert_signal_k1_3.vsd
Settings
- Temp. Min.: 20
°
C
- Temp Max.: 80
°
C
- switching hysteresis 5 % (from
100 %)
Message via relay
“
K1
”
(not inverted) IO Setup
→
K1 function: Limit Temp 6K
8.6 Timer
The device has a real time clock (not active in sensor operating modes). The clock is
backed up (Gold Cap) and has a reserve of 2 or 3 days after suf
fi
cient operation on a
voltage supply.
In principle, the timer function acts like a digital switch input (timer
“
On
”
closed contact
at inverting OFF). The same functions can be assigned to the timer switch as the digital
inputs (see IO Setup/Digital inputs
“
DI
”
).
The switch-on and switch-off times apply for every day of the week. If you set the timer
switch-on time before the current time, the assigned function is executed immediately
and continues until the switch-off time.
Inverting of the timer function
The timer function can be inverted by inverting the digital input to which the timer function
is assigned (see IO Setup/Digital inputs
“
DI
”
).
Menu overview
Parameter
Designation
15:05
Time
Time
Press the P-key
and set the hours with the UP / DOWN keys, press the
P-
key
to save.
Now the minutes
fl
ash and can be set with the UP / DOWN keys, press the
P-
key
to save.
Operating Instructions
UNIcon
CTG-150AVC
Programming
L-BAL-E287-GB 2015 Index 004
Part.-No.
29/36