Cooling
10K
Cooling function (only for two-position controller
2.03
)
Operating point: temperature = se/- Offset
Release point: Temperature around hysteresis below operating point
MODBUS sig.
17K
Setting via MODBUS register H01 Bit 14 (for
2.03
not possible)
10.11.2008
v_relais_k1_13_14.vsd
K1
14
13
K1
1
= energized, terminals 13 - 14 bridged
0
= de-energized, terminals 13 - 14 not bridged
Function
State controller
K1
1 = energized
0 = de-energized
Inverting
K1
OFF
ON
1K
Operation without fault
1
0
Switch off via digital input "DI" (no enable, display = "OFF")
0
1
Fault
0
1*
2K
Operation without fault
1
0
Switch off via digital input "DI" (no enable, display = "OFF")
1
0
Failure, external fault indication at "DI", Limit message
0
1*
3K
External fault indication via digital input "DI" (Display = "Ex-
ternal Error")
1
0
4K
Exceeding or undercutting the limits for modulation
1
0
5K
Exceeding or undercutting the limits for actual value
1
0
9K
Heating ON: temperature falling bellow se/- offset
1
0
10K
Cooling ON: temperature exceeding se/- offset
1
0
17K
MODBS register H01, if Bit 14 is set
1
0
*
In case of a failure, the relay can only be energised if the supply voltage is connected and the
device is functioning.
Operating Instructions
UNIcon
CTG-150AVC
Programming
L-BAL-E287-GB 2015 Index 004
Part.-No.
23/36