HR
Mode
Function/Setting
2.
00 01 03
H20
x
x
DI3 function: 0 = OFF, 1 = 1D, 2 = 3D, 3 = 5D
H21
x
x
DI3 Signal: 0 = n.a. (no asignement), 1 = D1, 3 = MODBUS, 3 = Timer
H22
x
x
DI-DI Relation: 0 = AND, 1 = OR
H23
x
x
x
AO1 function: 0 = OFF, 1 = 2A, 2 = 17A
H24
x
x
x
AO1 signal: 0 = n.a. (no asignement), 1 = A1
H30
x
Limit message temperature: 0 = OFF, 1 = ON
H31
x
Minimum temperature:
-500 = OFF, -500...1500
-50.0...150.0
°
C
(-580 = OFF, -580...3020
-58.0...302.0
°
F)
H32
x
Maximum temperature:
1500 = OFF, -500...1500
-50.0...150.0
°
C
(-580 = OFF, -580...3020
-58.0...302.0
°
F)
H33
x
Time delay limit message actual value: 0...120 (s)
H34
x
x
x
Limit message output voltage: 0 = OFF, 1 = ON
H35
x
x
x
Minimal output voltage: 0 = OFF, 0...100
0...10 V
H36
x
x
x
Maximum output voltage: 100 = OFF, 0...100
0...10 V
H37
x
x
x
Time delay limit message output voltage: 0...120 (s)
H40
x
x
Setpoint 1: -500...1500
-50.0...150.0
°
C (-580...3020
-58.0...302.0
°
F)
H44
x
x
x
Units of the display: 0 = SI units "metric", 1 = Imperial units (US) "inch"
H46
x
Temperature sensor type: 0 = KTY 81-210, 1 = PT 1000
H49
x
Offset temperature sensor:
-200...200
-20.0...20.0
°
C (-360...360
-36.0...36.0
°
F)
H51
x
x
Time: HIGHBYTE = hours, LOWBYTE = minutes
H52
x
x
Date: HIGHBYTE = month, LOWBYTE = day
H53
x
x
Year: 0...99
2000...2099
H54
x
x
Automatic summer time: 0 = OFF, 1 = ON
H56
x
x
Turn-on time: HIGHBYTE = hours, LOWBYTE = minutes
H57
x
x
Turn-off time: HIGHBYTE = hours, LOWBYTE = minutes
H59
x
x
Minimum18,0air switch-off: 0 = OFF, -100...100
-10.0...10.0
°
C (-180...180
-
18.0...18.0
°
F)
H60
x
x
Controlfunction: 1 = cooling/0 = heating
H62
x
Offset36,0setpoint digital output to setpoint P-controller: 0 = OFF, -200...200
-
20.0...20.0 K (-360...360
-36.0...36.0
°
F)
H63
x
Hysteresis: 0...200
0,0...20, 0 K (0...360
0,0...36,0
°
F)
*