25.09.17
Date
Date
To set the date follow the same method as for
“
Time
”
. The date setting
consists of day,month and year.
Example for: 25. September 2017
Entering the date is only required if automatic summer time adjustment is
used.
OFF
Summertime Auto
Automatic summer time
The summertime automatic is factory set to
“
OFF
”
, i.e. switched off. When the
summertime automatic is activated the device automatically switches be-
tween daylight saving time and wintertime.
23:00
ON
Turn-on time
05:00
OFF
Turn-off time
Information
Automatic daylight saving time only applies to countries in the Northern hemisphere.
The time is put forward from 2:00 am to 3:00 am on the last Sunday in March and put
back from 3:00 am to 2:00 am on the last Sunday in October.
If other dates for the switch over between daylight saving time and winter time are
required, the clock must be changed by hand (manually) on the respective date.
8.7 MODBUS SLAVE
8.7.1 Address and interface parameters
Addressing and con
fi
guration of the MODBUS Slave interface.
Via this interface the device can be networked with a master building control system, the
device then operates as a pure Slave and uses the MODBUS-RTU protocol.
The connection is made to the terminals
“
A (D+)
”
,
“
B (D-)
”
of the MODBUS Slave
interface (see installation / RS-485 interfaces for MODBUS RTU).
Menu overview
Function
Designation
247
Bus Address
Bus Address
The device address is factory set to the highest available MODBUS address:
247.
Setting range MODBUS Address: 1 - 247.
19200
UART Baudrate
UART Baudrate
Setting transfer rate
Valid values: 4800, 9600, 19200, 38400, 115200
Factory setting: 19200
Operating Instructions
UNIcon
CTG-150AVC
Programming
L-BAL-E287-GB 2015 Index 004
Part.-No.
30/36