9.2 Connection diagram
GND
A GND
1(+) 2( )
+U
S
MCTE04K2
25.04.2018
CTG-150AVC
+
+
10...24 V DC
+
R
i
= 4 kΩ
0 1
Spannungsversorgung
Voltage supply
10...24 V DC
(10...24 V: I
max
= 28 mA)
1
U
S
Ausgang
Output
0...10 V
(I
max
= 0.3 mA @ U
S
10 V)
(I
max
= 10 mA @ U
S
13...24 V)
2
U
out
+
-
q
TF..
TF
TF
KTY 81-210
PT 1000
4
ID2
A
(D+)
B
(D-)
GND
ID1
A
(D+)
B
(D-)
GND
J1
GND
MODBUS
Slave
(RS-485)
5
Ad
d
re
ssi
n
g
13
14
Kontaktbelastung
Contact rating
max. AC 250 V 2 A
MODBUS Slave
K1
A1
D1
3
Digital Eingang
Digital input
6
1
Voltage supply 10...24 V DC
2
Output 0...10 V
3
digital input (voltage ON/OFF)
4
Temperature sensor KTY81-210 or PT 1000
5
MODBUS Slave interface RS-485 (J1 plugged = Bus terminating resistor 150
Ω
active)
6
Contact rating max. AC 250 V 2 A
9.3 Dimensions [mm]
Operating Instructions
UNIcon
CTG-150AVC
Enclosure
L-BAL-E287-GB 2015 Index 004
Part.-No.
35/36