3.2
Maintenance
The device must be checked for soiling and, if necessary, cleaned in periodic intervals.
3.3
Transport
•
The device is packed ex factory to suit the transport method previously agreed.
•
Always use the original packaging materials when transporting the device.
•
Avoid shocks and impacts to the device during the transport.
•
During manual handling the human lifting and carrying restrictions must be observed and adhered
to.
3.4
Storage
•
The device must be stored in its original packaging in a dry and weather-proof room.
•
Avoid exposure to extreme heat and cold.
•
Avoid over-long storage periods (we recommend a maximum of one year).
3.5
Disposal / recycling
Disposal must be carried out professionally and in an environmentally friendly way in accordance with
the respective national legal stipulations.
"
Separate the materials by type and in an environmentally friendly way.
"
If necessary, commission a specialist company with the waste disposal.
4
Mounting
4.1
General notes
Attention!
The following points must be complied with during the mechanical installation to avoid causing a defect
in the device due to assembly errors or environmental in
fl
uences:
•
Before installation remove the device from the packing and check for any possible shipping
damage!
•
Assemble the device on a clean and stable base. Do not distort during assembly! Use the
appropriate mounting devices for proper installation of the unit!
•
Do not mount equipment on vibrating base!
•
When mounted onto lightweight walls, there must be no impermissibly high vibrations or shock
loads. Any banging shut of doors that are integrated into these lightweight walls, can result in
extremely high shock loads. Therefore, we advise you to decouple the devices from the wall.
•
Do not allow drilling chips, screws and other foreign bodies to reach the device interior!
•
The device should be installed in a location where it will not be disturbed, but at the same time can
be easily accessed!
•
Depending on the housing model use supplied stoppers for cable inlets, cut off necessary cable
inlets respectively to the cable diameter. Or alternative use cable inlet for cable glands. Any cable
ducts openings not used must be sealed!
•
Care must be taken to avoid direct radiation from the sun!
•
The device is designed for vertical installation (cable inlet down). A horizontal or reclined installation
is only permissible after technical release of the manufacturer!
•
Be sure to observe proper heat dissipation (
Technical data, heat dissipation).
4.2
Minimum space requirement
In order to ensure suf
fi
cient ventilation of the device, clearance on all sides of at least 50 mm has to
be maintained to the housing walls, switch cabinet doors, wiring ducts, etc. The same clearance
applies to the installation of several devices next to each other.
When installing several devices on top of each other, the danger of reciprocal heating exists. This
layout is only then permissible when the air suctioned from the upper unit does not become warmer
than the permissible ambient temperature (
Technical data). I.e., a correspondingly larger clearance
or thermal shielding is required.
Operating Instructions
ALARMcon
–
model series UTE-32A-L
Mounting
L-BAL-E251-GB 1542 Index 002
Part.-No. 00163281
7/44