Each alarm input
“
D1
”
...
“
D5
”
can be allocated to one alarm group. In this way, different alarm pause
times can be obtained for digital inputs.
–
The settings of the alarm pause times for the alarm groups are made in the
“
ALARMcon Setup
”
under menu items
“
Al. Pause time1...5
”
Menu of alarm inputs
Alarm
input
Status
Function
(message display)
Alarm delay
Inverting
Alarm group
factory set-
ting
Setting
factory set-
ting
Setting
factory set-
ting
Setting
factory set-
ting
Setting
D1
OFF
1
2 min
OFF
1
D2
OFF
2
2 min
OFF
1
D3
OFF
3
2 min
OFF
1
D4
OFF
4
2 min
OFF
1
D5
OFF
5
2 min
OFF
1
Code
Message
1
Ventilation
2
Motor protection
3
feeder
4
FI circuit breaker
5
Intrusion
6
Cullet
7
Smoke Detector
8
Water Detector
9
Gas Detector
10
External alarm
11
Alarm Cot 1
12
Alarm Cot 2
13
Alarm Cot 3
14
Alarm Cot 4
15
Alarm Cot 5
16
Failure
8.3.4
GSM alarming
GSM alarming
In connection with a GSM modem, an alarm signal to mobile phones is possible. A GSM
and 4 alarm numbers can be set.
Operating Instructions
ALARMcon
–
model series UTE-32A-L
Setting for operation
L-BAL-E251-GB 1542 Index 002
Part.-No. 00163281