Alarm and fault indications
Reminder of alarm test (no error message)
Test alarms!
Test alarms!
An alarm test reminder is given automatically every week. Display
“
Test alarms!
”
alternately with the standard display.
This signal is reset again for a week on running an alarm test.
A regular function test of the alarm transmitter (alarm horn,
fl
ashing light and the signal,
e.g via telephone dialling device) is necessary!
Alarm test
See Info menu
“
Alarm test
”
This signal is reset again for a week on running an alarm test. For this, set alarm test
brie
fl
y to
“
ON
”
, then back to
“
OFF
”
and check whether an alarm is given by horn,
fl
ashing light or telephone dialling device!
As long as it is
“
ON
”
the alarm horn,
fl
ashing light and the relay for the message is
activated, for example by telephone dialling device (function also in switch position
“
0
”
).
Fault indications
Display
Possible cause
Adjustment
All displays remain con-
stantly off
•
No mains voltage and no emergency
power supply by the accumulator.
•
Display line not plugged in.
•
Defect in device.
Check:
•
Power supply, internal fuse switch
accumulator, connection accumulator.
•
Display connection after removing the
housing cover.
•
If after checking no remedy possible.
Replacement necessary.
Power failure
If no power supply, the display for charging
state of the display
fl
ashes at
fi
rst
Alarming sequence at factory settings in
the
“
ALARMcon Setup
”
After approx. 2 minutes the message
“
Power failure
”
appears with alarming by
alarm horn and
fl
ashing light.
After another approx. 2 minutes the signal
is also sent via the relay, e.g. for alarming
via telephone dialling device.
Check:
•
Mains connection
•
line fuse
•
Device fuse
Reset
•
Main switch in position
“
Horn OFF
”
(when setting to "AutoAcknowl." in the
"ALARMcon Setup" no acknowledge-
ment is necessary after repairing the
fault).
05.04 Freshair
05.04 Freshair
05.04 Freshair
Battery error
Emergency power supply via internal accu-
mulator not available.
Check:
•
Switch for accumulator in the terminal
compartment?
•
Connection of accumulator after re-
moving the top part of the housing
Reset
1. Turn off mains voltage.
2. Switch battery off and then back on.
3. Turn on mains voltage
"
Battery (replace accumulator).
Battery error
After a few minutes delay, the message
“
Battery error
”
appears with alarming by
alarm horn and
fl
ashing light.
Alarming sequence at factory settings in
the
“
ALARMcon Setup
”
.
Battery error
After another approx. 2 minutes the signal
is also sent via the relay, e.g. for alarming
via telephone dialling device.
Operating Instructions
ALARMcon
–
model series UTE-32A-L
Alarm and fault indications
L-BAL-E251-GB 1542 Index 002
Part.-No. 00163281
33/44