Adjustment E2
Adjustment E2
Adjustment (offset) for
“
E1
”
sensor value. Enter difference in Kelvin reference measuring
device
Factory setting: 0.0 K
Setting range: -10...+10K
Alarm correction
Alarm correction
Supply air temperature-dependent component for the overtemperature alarm trigger of the
stalls.
The setting of the
“
alarm correction
”
takes place in networked systems separately on
every ventilation computer under
“
Alarm difference
”
i.e. this setting then does not work on
the ALARMcon!
The
“
alarm correction
”
should prevent too early an alarm at relatively high outdoor temper-
atures, constant adjustment of the
“
Alarm max.
”
temperature is no longer necessary.
The cot temperature must increase above
“
Alarm max.
”
and above supply air temperature
+ alarm correction in order for an overtemperature alarm to be triggered.
Earliest alarm point = supply air tempe alarm correction
Factory setting: 5 K
Adjustment range: 0...10K
Examples in different temperature constellations
Setting
“
Alarm max. 1
”
[
°
C]
26
26
26
26
Setting
“
Alarm correction
”
[K]
4
4
4
4
Supply air temperature [
°
C]
25
21
28
28
Air temperature in the cot 1 [
°
C]
27
27
30
33
Alarm message
NO
YES
NO
YES
Delay mains
Delay mains
Alarm time delay in mains failure
Time span between detection and signalling at mains failure
Factory setting: 2 min
Setting range: 0...250 min
Delay tel.
Delay tel.
Time span before an alarm message is signalled by the telephone dialling device.
If a fault is detected (e.g. overtemperature, undertemperature), the alarm message is
fi
rst
given by alarm horn and
fl
ashing light.
In case of mains fault and alarm message via a digital input (D1 .. D5) this only takes
place after an adjustable time delay.
The message via the relay, e.g. for activation of a telephone dialling device, takes place
subsequently, i.e.by the adjustable time span
“
delay tel
”
after sounding of the horn and
lighting of the
fl
ashing light.
Factory setting: 2 min
Setting range: 0...250 min
Operating Instructions
ALARMcon
–
model series UTE-32A-L
Setting for operation
L-BAL-E251-GB 1542 Index 002
Part.-No. 00163281
23/44