26
Installation and operating instructions
5.4.6 Miniature circuit breaker
You must safeguard each inverter with an individual miniature circuit breaker in
order that the inverter can be disconnected safely.
No consumer load should be applied between the miniature circuit breaker and the
inverter. Use dedicated circuit breakers with load switch functionality for load
switching. The selection of the miniature circuit breaker rating depends on the wiring
design (wire cross-section area), cable type, wiring method, ambient temperature,
inverter current rating, etc. Derating of the miniature circuit breaker rating may be
necessary due to self-heating or if exposed to heat.
The maximum output current of the inverters can be found in the following table.
5.5 DC Connection
• Before connecting the PV generator, ensure that the DC-switch is switched off and
that it cannot be reactivated.
• Do not disconnect the DC connectors under load.
Type
TLC 10K
TLC 15K
TLC 17K
TLC 20K
Max. output current
16A
24A
25.8A
30A
Recommended fuse type gL/gG or
comparable automatic circuit breaker rating
25A
40A
40A
40A
DANGER
Danger to life due to fire!
DANGER
Danger to life due to high voltages in the inverter!