Installation and operating instructions
4 Mounting
4.1 Ambient conditions
1
Be sure the inverter is installed out of the reach of children.
2
Mount the inverter in areas where it cannot be touched inadvertently.
3
Ensure good access to the inverter for installation and possible service.
4 Observe the minimum clearances to walls, other inverters, or objects as
follows to ensure that heat can escape.
Clearances for one inverter
Clearances for multiple inverters
5
The ambient temperature should be below 40°C to ensure optimal operation.
Direction Min. clearance
(
mm
)
above
200
below
500
sides
300