background image

PREMIER SX INSTALLATION MANUAL.  

 

 

 

 

 

Approved Document No: GLT.MAN-101

 

 

 

PAGE 4

 

Issue : 1.95         Authorised: GH      Date: 09/06/2004

 

 

2. FIRST FIX 

 

All wiring must be installed to meet BS5839: Pt1: 2002 and BS 7671 (Wiring Regs) standards.  
Other National standards of fire alarm system installation should be adhered to where 
applicable. 

 

2.1 RECOMMENDED CABLE TYPES AND THEIR LIMITATIONS 

 

Screened cables should be used throughout the installation to help shield the Panel from outside 
interference and ensure EMC compatibility. 

 

The two categories of cable according to BS5839: Pt1: 2002, Clause 26 “Fire Detection and Alarm 
Systems for Buildings (Code of Practice for System Design, Installation and Servicing)” are: 

 

Standard fire resisting cable – to PH30 classification of EN 50200 
Enhanced fire resisting cable – to PH120 classification of EN 50200 
(Note that all cables should be at least 1mm

2

 cross section 

 

On the Optima Panel the general recommendation would be to use standard fire resistant cable, such 
as Firetuff

 , FP200 or an equivalent. These cables are screened, and will provide good ECM 

shielding when properly grounded at the panel.  Certain system specifications may demand the use 
of a particular type of cable and due regard should be paid to this fact. 

 

Depending on the environment, the cables may need mechanical protection (such as a conduit). 
 

2.2 MAINS WIRING RECOMMENDATIONS 
 

The Mains supply to the FACP is fixed wiring, using 

Fire resisting

 3-core cable (Between 1 mm² and 

2.5mm²) or a suitable 3-conductor system, fed from an isolating double pole switch fused spur, fused 
at 3A.

  IT SHOULD NOT BE CONNECTED THROUGH AN RCD.

 This should be secure from 

unauthorised operation and be marked ‘FIRE ALARM: DO NOT SWITCH OFF’.  The supply must be 
exclusive to the Fire Panel. 

MAKE SURE ANY SPARE ENTRY HOLES ARE COVERED WITH THE 

GROMMETS PROVIDED

 

 

For information on how to connect Mains to the Panel’s Power Supply PCB, see page 8. 
Also refer to rating information inside the FACP. 
 

2.3 DETECTOR CIRCUIT WIRING DIAGRAM 
 

The Premier SX comes with one, two, four, six or eight Detection circuits (Zones).  A maximum of 32 
devices (i.e. smoke detectors, heat detectors, or Manual Call Points) can be fitted to each circuit. 

ALL DEVICES MUST BE POLARISED.

 

 

 

Typical detector circuit wiring (Premier Detectors)

 

 

R-

L+

L-

L-

R-

L+

L-

L-

R-

L+

L-

L-

R-

L+

L-

L-

+

- -

+

+

- -

+

END of

LINE 

DIODE

1N4002

CALL

POINT

CALL

POINT

ZONE +

ZONE -

Do not spur devices because they will not be monitored

Diode

Base

 

or 

R-

L+

L-

L-

R-

L+

L-

L-

R-

L+

L-

L-

R-

L+

L-

L-

END of

LINE 

DIODE

1N4002

+

- -

+

CALL

POINT

+

- -

+

CALL

POINT

ZONE +

ZONE -

If ALL the call points are connected to the start of the zone, then 
conventional bases can be used instead of diode bases.

 

Summary of Contents for NPSX1

Page 1: ...INSTALLATION MANUAL...

Page 2: ...X TO THE WALL 4 CONNECTING MAINS BATTERY POWER 8 4 1 CONNECTING MAINS POWER 4 2 CONNECTING THE BATTERIES 5 FIELD DEVICE TERMINATION 9 5 1 TERMINATING THE DETECTION AND ALARM SOUNDER CIRCUITS 5 2 AUXIL...

Page 3: ...ned with the property at an early stage in case he has any special requirements If in doubt read BS 5839 Pt 1 2002 Fire Detection and Fire Alarm Systems for buildings Code of Practice for System Desig...

Page 4: ...be paid to this fact Depending on the environment the cables may need mechanical protection such as a conduit 2 2 MAINS WIRING RECOMMENDATIONS The Mains supply to the FACP is fixed wiring using Fire r...

Page 5: ...e OUT to non stripe side of continuity diode Some makes will connect the ve to a 470R load resistor or a polarisation diode to enable the detector to work correctly Our new Fyreye detectors pronounced...

Page 6: ...ndition In a fault condition the output relay turns off to ensure failsafe operation even in the event of total power loss That is the normally open contact will be closed when there is no fault and o...

Page 7: ...oved but subsequently not used it should be covered up The 230Va c Mains cable must be fed into the enclosure via one of the cable entries at the top right corner of the back box Refer to Connecting t...

Page 8: ...nterference Once the mains is connected the protective cover should be replaced BEFORE turning on the mains power This will minimise the chance of electric shock from the PCB MAKE SURE ANY SPARE ENTRY...

Page 9: ...cable grounding plate The Detector and Sounder circuits should be connected to the appropriate connector block on the Termination PCB as shown in Figure 6 below All screens should be fed through the g...

Page 10: ...Alarm sounder outputs being activated can be programmed into the panel by the Engineer This is a particularly useful feature for schools nightclubs and other public places where the nuisance and panic...

Page 11: ...continue running but doesn t want spurious false alarms The panel will respond in the usual manner to any events in any non disabled zones 7 2 TO PROGRAMME ZONE OR SOUNDERS AS DISABLED Any number of...

Page 12: ...Zone or turn the control key switch to off position to exit test mode 9 GENERAL FAULT FINDING 9 1 ZONE FAULTS Open circuit faults will be indicated by zone s fault LED flashing In case of a short cir...

Page 13: ...Charging Voltage The charging voltage should be 28 4V off load at 20o C If it has been altered reset using potentiometer VR1 5 Overcharged Batteries Remove the batteries and measure the voltage If it...

Page 14: ...al Detector 0 0001 Amp 100 A Typical Example A system comprises of 20 ionisation detectors 14 bells and the required standby is 24 hours It will need to operate in alarm for hour Calculate the battery...

Page 15: ...ns bells 11 CLASS CHANGE Join terminals to activate sounders 12 FIRE RELAY NO CM NC Activates on fire including test mode 13 FAULT RELAY NO CM NC Normally powered ie NO is closed with no fault 14 BATT...

Page 16: ...AL 18 32 V SYSTEM VOLTAGE RIPPLE 2V PK PK MAX CHARGER SIZE UP TO 7AH in 24 Hours ZONE VOLTAGE 21V DC NOMINAL 20 22 5V SOUNDER ALARM OUTPUTS 2 x 400mA 24V DC Nominal AUXILIARY FAULT OUTPUT 1 x RELAY SE...

Reviews: