background image

PREMIER SX INSTALLATION MANUAL.  

 

 

 

 

 

Approved Document No: GLT.MAN-101

 

 

 

PAGE 11

 

Issue : 1.95         Authorised: GH      Date: 09/06/2004

 

 

 

6.3 DELAY INDICATION AND OVERRIDE 

 
If a delay is set, the fire panel will light the General Disablement LED and Delay (DEL) LED to 
indicate that the sounders are delayed. If an alarm occurs, the fire LEDs will light as usual, but the 
sounders will not start until the delay period has expired. After the delay period, the Gen Disablement 
and Delay LEDs will extinguish & the sounders will start. 

  

Pressing the ‘sounder override’ switch will override the delay at any time and results in the sounders 
being turned on immediately. 

 

If on investigation, the panel was activated by a false alarm, turn the keyswitch to Controls Enabled, 
and press the reset button. This will return the system to normal, without the sounders being 
activated. (Assuming the cause of the false alarm has been removed). 

 

The delay can be removed by either returning the rotary switch to position 0, or by turning keyswitch 
to Controls Active, pressing Engineer, then pressing Delay override. (Continuing to press delay 
override will toggle the delay on & off). 
 

7. ZONE DISABLEMENT 

 
7.1 WHY USE ZONE DISABLEMENT 

 

To aid commissioning and assist routine maintenance checks, any of the zones or the sounder 
circuits can be disabled. 

 

When a zone (or sounder cct) is disabled, the panel will not respond to any fault or fire signals it 
receives from that zone. This might be used if the system requires routine maintenance, and the 
customer needs the system to continue running, but doesn’t want spurious false alarms. 

 

The panel will respond in the usual manner to any events in any non-disabled zones. 

 
7.2 TO PROGRAMME ZONE (OR SOUNDERS) AS DISABLED 

 
Any number of zones (or the sounders) can be disabled, but it is good practice to only disable one 
zone at a time. 

 

1. 

Insert and turn control key to enabled position; 

 

2. 

Press Engineer switch and the GENERAL DISABLEMENT LED will come on (flashing fast); 

 

3. 

Press Scroll switch and the GENERAL DISABLEMENT LED will flash slowly. The panel is now 
in SELECT DISABLEMENT MODE. 

 

4. 

Press scroll button again. Zone 1 DISABLEMENT LED will be lit. Continue to press scroll until 
the desired Zone or sounder is lit.  Press the Engineer button. The GENERAL DISABLEMENT 
LED will be lit constantly indicating that this zone (or sounder) is now disabled. 

 

5. 

If more than one zone needs to be disabled, then press scroll again until the required zone is 
selected. 

 

6. 

If the panel needs to be taken out of SELECT DISABLEMENT MODE (eg to silence a fault on 
another part of the system), turn the keyswitch off, then back on again. 

 

7. 

Once all the work has been done the zones need to be enabled again. If the panel is still in 
SELECT DISABLEMENT MODE, jump to paragraph 8, otherwise, turn the keyswitch to 
controls enabled, press engineer button (GENERAL DISABLEMENT LED will flash fast). Press 
scroll and it will return to being on steady. The panel is now in SELECT DISABLEMENT MODE 

 

8. 

 Press the scroll button until the disabled zone has been selected. Press engineer button. 
Scroll to any other disabled zone and enable in the same way. When all zones are enabled 
again, the GENERAL DISABLEMENT LED will flash slowly. Turn the keyswitch to off to return 
the system to normal.  

 

 
 
 
 

Summary of Contents for NPSX1

Page 1: ...INSTALLATION MANUAL...

Page 2: ...X TO THE WALL 4 CONNECTING MAINS BATTERY POWER 8 4 1 CONNECTING MAINS POWER 4 2 CONNECTING THE BATTERIES 5 FIELD DEVICE TERMINATION 9 5 1 TERMINATING THE DETECTION AND ALARM SOUNDER CIRCUITS 5 2 AUXIL...

Page 3: ...ned with the property at an early stage in case he has any special requirements If in doubt read BS 5839 Pt 1 2002 Fire Detection and Fire Alarm Systems for buildings Code of Practice for System Desig...

Page 4: ...be paid to this fact Depending on the environment the cables may need mechanical protection such as a conduit 2 2 MAINS WIRING RECOMMENDATIONS The Mains supply to the FACP is fixed wiring using Fire r...

Page 5: ...e OUT to non stripe side of continuity diode Some makes will connect the ve to a 470R load resistor or a polarisation diode to enable the detector to work correctly Our new Fyreye detectors pronounced...

Page 6: ...ndition In a fault condition the output relay turns off to ensure failsafe operation even in the event of total power loss That is the normally open contact will be closed when there is no fault and o...

Page 7: ...oved but subsequently not used it should be covered up The 230Va c Mains cable must be fed into the enclosure via one of the cable entries at the top right corner of the back box Refer to Connecting t...

Page 8: ...nterference Once the mains is connected the protective cover should be replaced BEFORE turning on the mains power This will minimise the chance of electric shock from the PCB MAKE SURE ANY SPARE ENTRY...

Page 9: ...cable grounding plate The Detector and Sounder circuits should be connected to the appropriate connector block on the Termination PCB as shown in Figure 6 below All screens should be fed through the g...

Page 10: ...Alarm sounder outputs being activated can be programmed into the panel by the Engineer This is a particularly useful feature for schools nightclubs and other public places where the nuisance and panic...

Page 11: ...continue running but doesn t want spurious false alarms The panel will respond in the usual manner to any events in any non disabled zones 7 2 TO PROGRAMME ZONE OR SOUNDERS AS DISABLED Any number of...

Page 12: ...Zone or turn the control key switch to off position to exit test mode 9 GENERAL FAULT FINDING 9 1 ZONE FAULTS Open circuit faults will be indicated by zone s fault LED flashing In case of a short cir...

Page 13: ...Charging Voltage The charging voltage should be 28 4V off load at 20o C If it has been altered reset using potentiometer VR1 5 Overcharged Batteries Remove the batteries and measure the voltage If it...

Page 14: ...al Detector 0 0001 Amp 100 A Typical Example A system comprises of 20 ionisation detectors 14 bells and the required standby is 24 hours It will need to operate in alarm for hour Calculate the battery...

Page 15: ...ns bells 11 CLASS CHANGE Join terminals to activate sounders 12 FIRE RELAY NO CM NC Activates on fire including test mode 13 FAULT RELAY NO CM NC Normally powered ie NO is closed with no fault 14 BATT...

Page 16: ...AL 18 32 V SYSTEM VOLTAGE RIPPLE 2V PK PK MAX CHARGER SIZE UP TO 7AH in 24 Hours ZONE VOLTAGE 21V DC NOMINAL 20 22 5V SOUNDER ALARM OUTPUTS 2 x 400mA 24V DC Nominal AUXILIARY FAULT OUTPUT 1 x RELAY SE...

Reviews: