background image

PREMIER SX INSTALLATION MANUAL.  

 

 

 

 

 

Approved Document No: GLT.MAN-101

 

 

 

PAGE 7

 

Issue : 1.95         Authorised: GH      Date: 09/06/2004

 

 

 

3. MOUNTING THE FIRE ALARM PANEL 

 
It is recommended that the panels door be removed to avoid accidental damage. Also, the 
termination PCB could be removed and stored in a safe place, while fixing the back box to the wall. 
 

3.1 PLANNING CABLE ENTRY

 

 
Fig.2 below shows the location of the cable entries to facilitate planning of wiring (home runs) to be 
brought to the panel.  
 
The grommets can be easily removed by a push from inside the control panel box. 
 
If a grommet is removed, fill the hole with a brass cable gland.  If any knockout is removed, but 
subsequently not used, it should be covered up. 
 
The 230Va.c. Mains cable must be fed into the enclosure via one of the cable entries at the top right 
corner of the back box.  (Refer to “Connecting the Mains” on Page 8). 
 

3.2 FIXING THE BACK BOX TO THE WALL 
 
Figure 2:  Plan view inside the enclosure without PCBs. Side view for surface / flush installation.

 

 

Wall Mount

Flush Mount

12 x 19mm grommet cable entries

2 x 19mm 

knock-out

cable entries

355mm

275mm

250mm

195mm

60 x 20mm
back cable 
entry

60 x 20mm
back cable 
entry

73mm

 

 
 
 
Fix the enclosure to the wall using the three mounting holes provided. 
 
Check the build & condition of the wall to decide a suitable screw fixing.  
 
The mounting holes are designed for No 8 roundhead or countersunk woodscrews (or similar). 
 
Remove any debris from the enclosure.  
 
Take care not to damage the FACP during installation. 
 
 

Summary of Contents for NPSX1

Page 1: ...INSTALLATION MANUAL...

Page 2: ...X TO THE WALL 4 CONNECTING MAINS BATTERY POWER 8 4 1 CONNECTING MAINS POWER 4 2 CONNECTING THE BATTERIES 5 FIELD DEVICE TERMINATION 9 5 1 TERMINATING THE DETECTION AND ALARM SOUNDER CIRCUITS 5 2 AUXIL...

Page 3: ...ned with the property at an early stage in case he has any special requirements If in doubt read BS 5839 Pt 1 2002 Fire Detection and Fire Alarm Systems for buildings Code of Practice for System Desig...

Page 4: ...be paid to this fact Depending on the environment the cables may need mechanical protection such as a conduit 2 2 MAINS WIRING RECOMMENDATIONS The Mains supply to the FACP is fixed wiring using Fire r...

Page 5: ...e OUT to non stripe side of continuity diode Some makes will connect the ve to a 470R load resistor or a polarisation diode to enable the detector to work correctly Our new Fyreye detectors pronounced...

Page 6: ...ndition In a fault condition the output relay turns off to ensure failsafe operation even in the event of total power loss That is the normally open contact will be closed when there is no fault and o...

Page 7: ...oved but subsequently not used it should be covered up The 230Va c Mains cable must be fed into the enclosure via one of the cable entries at the top right corner of the back box Refer to Connecting t...

Page 8: ...nterference Once the mains is connected the protective cover should be replaced BEFORE turning on the mains power This will minimise the chance of electric shock from the PCB MAKE SURE ANY SPARE ENTRY...

Page 9: ...cable grounding plate The Detector and Sounder circuits should be connected to the appropriate connector block on the Termination PCB as shown in Figure 6 below All screens should be fed through the g...

Page 10: ...Alarm sounder outputs being activated can be programmed into the panel by the Engineer This is a particularly useful feature for schools nightclubs and other public places where the nuisance and panic...

Page 11: ...continue running but doesn t want spurious false alarms The panel will respond in the usual manner to any events in any non disabled zones 7 2 TO PROGRAMME ZONE OR SOUNDERS AS DISABLED Any number of...

Page 12: ...Zone or turn the control key switch to off position to exit test mode 9 GENERAL FAULT FINDING 9 1 ZONE FAULTS Open circuit faults will be indicated by zone s fault LED flashing In case of a short cir...

Page 13: ...Charging Voltage The charging voltage should be 28 4V off load at 20o C If it has been altered reset using potentiometer VR1 5 Overcharged Batteries Remove the batteries and measure the voltage If it...

Page 14: ...al Detector 0 0001 Amp 100 A Typical Example A system comprises of 20 ionisation detectors 14 bells and the required standby is 24 hours It will need to operate in alarm for hour Calculate the battery...

Page 15: ...ns bells 11 CLASS CHANGE Join terminals to activate sounders 12 FIRE RELAY NO CM NC Activates on fire including test mode 13 FAULT RELAY NO CM NC Normally powered ie NO is closed with no fault 14 BATT...

Page 16: ...AL 18 32 V SYSTEM VOLTAGE RIPPLE 2V PK PK MAX CHARGER SIZE UP TO 7AH in 24 Hours ZONE VOLTAGE 21V DC NOMINAL 20 22 5V SOUNDER ALARM OUTPUTS 2 x 400mA 24V DC Nominal AUXILIARY FAULT OUTPUT 1 x RELAY SE...

Reviews: