background image

PREMIER SX INSTALLATION MANUAL.  

 

 

 

 

 

Approved Document No: GLT.MAN-101

 

 

 

PAGE 12

 

Issue : 1.95         Authorised: GH      Date: 09/06/2004

 

 

8. ZONE TEST 

 
8.1 WHY USE ZONE TEST

 

 

To aid commissioning and assist routine maintenance check, a non-latching ‘one man test’ facility is 
available. 
 
When a detector or manual call point is triggered on any zone in Test, the Alarm sounders operate for 
approximately seven seconds on and seven seconds off.  This cycle continues until the cause of the 
Alarm is removed (either by the test smoke clearing from the detector or the manual call point being 
reset), at which point, the detector circuit also automatically resets. 
 
Should an Alarm occur on a zone that is not programmed to test, the Alarm will be processed in the 
normal way.  The testing of the zone in test will temporarily be suspended until the Alarm(s) from the 
other zones are reset.  At this point, zone retesting may resume. 
 

8.2 TO PROGRAMME ZONE IN TEST 

 
NOTE:  Only 

one zone

 can be programmed in test at any one time. 

 
1.  Insert and turn control key to enabled position; 

 

2.  Press engineer switch until the General Zone test LED is on (flashing fast); 

 

3.  Enter Engineer Code 4114 and then the General Zone Test LED is on (flashing slow); 

 

4.  Press scroll switch and Zone one fault LED will flash in synchronisation with the General Zone 

test; 

 

5.  Press scroll button to the desired Zone for test.  Once the desired Zone LED is flashing, this 

Zone is now in test mode. 

 

6.  Once testing of that zone is completed, press scroll button to move to another Zone or turn the 

control key switch to off position to exit test mode. 

 

9. GENERAL FAULT FINDING 

 
9.1 ZONE FAULTS

 

 
Open circuit faults will be indicated by zone(s) fault LED flashing.  In case of a short circuit fault, then 
the Zone(s) Fault LED will be accompanied by the Short Circuit Fault LED.  In both cases, the 
internal Fault Buzzer will sound and the General Fault LED will be lit. 
 
The Zone Faults are non-latching faults.  That is, if the fault disappears, the panel will automatically 
reset itself. (After a short delay of up to a minute) 
 

Suggested Action

 

 

a) 

Disconnect the wiring for the zone showing fault, and refit the end of line diode at that zone 
terminal in the panel.  If the fault condition for that zone clears, this confirms there is a wiring 
fault. 

 

b) 

Double-check the wiring and the end of line diode on the zone.  Trace the fault with 
consideration for the type of fault indicated.(HINT: splitting the cable half way down the zone, 
and fitting the end of line diode to the new end point helps to determine which section of cable 
is giving the fault) 

 

Note:  A common fault is a detector head badly seated in a base that is not making the 
connection. 

 

c) 

A short circuit on a zone could be caused by the end of line diode being fitted backwards. 

 

d) 

Check that the detectors are compatible with this FACP. Note that some makes of detector will 
require a series resistor or diode to be fitted to work properly. There is usually a spare 
connector on the base to accommodate this (check instructions that came with the detector). 

 

e) 

Measure the resistance of the zone cabling (Remove from panel and short out end of line). 
Ideally this should be less than 50 ohms. Above 70 ohms may cause an open circuit fault. 

Summary of Contents for NPSX1

Page 1: ...INSTALLATION MANUAL...

Page 2: ...X TO THE WALL 4 CONNECTING MAINS BATTERY POWER 8 4 1 CONNECTING MAINS POWER 4 2 CONNECTING THE BATTERIES 5 FIELD DEVICE TERMINATION 9 5 1 TERMINATING THE DETECTION AND ALARM SOUNDER CIRCUITS 5 2 AUXIL...

Page 3: ...ned with the property at an early stage in case he has any special requirements If in doubt read BS 5839 Pt 1 2002 Fire Detection and Fire Alarm Systems for buildings Code of Practice for System Desig...

Page 4: ...be paid to this fact Depending on the environment the cables may need mechanical protection such as a conduit 2 2 MAINS WIRING RECOMMENDATIONS The Mains supply to the FACP is fixed wiring using Fire r...

Page 5: ...e OUT to non stripe side of continuity diode Some makes will connect the ve to a 470R load resistor or a polarisation diode to enable the detector to work correctly Our new Fyreye detectors pronounced...

Page 6: ...ndition In a fault condition the output relay turns off to ensure failsafe operation even in the event of total power loss That is the normally open contact will be closed when there is no fault and o...

Page 7: ...oved but subsequently not used it should be covered up The 230Va c Mains cable must be fed into the enclosure via one of the cable entries at the top right corner of the back box Refer to Connecting t...

Page 8: ...nterference Once the mains is connected the protective cover should be replaced BEFORE turning on the mains power This will minimise the chance of electric shock from the PCB MAKE SURE ANY SPARE ENTRY...

Page 9: ...cable grounding plate The Detector and Sounder circuits should be connected to the appropriate connector block on the Termination PCB as shown in Figure 6 below All screens should be fed through the g...

Page 10: ...Alarm sounder outputs being activated can be programmed into the panel by the Engineer This is a particularly useful feature for schools nightclubs and other public places where the nuisance and panic...

Page 11: ...continue running but doesn t want spurious false alarms The panel will respond in the usual manner to any events in any non disabled zones 7 2 TO PROGRAMME ZONE OR SOUNDERS AS DISABLED Any number of...

Page 12: ...Zone or turn the control key switch to off position to exit test mode 9 GENERAL FAULT FINDING 9 1 ZONE FAULTS Open circuit faults will be indicated by zone s fault LED flashing In case of a short cir...

Page 13: ...Charging Voltage The charging voltage should be 28 4V off load at 20o C If it has been altered reset using potentiometer VR1 5 Overcharged Batteries Remove the batteries and measure the voltage If it...

Page 14: ...al Detector 0 0001 Amp 100 A Typical Example A system comprises of 20 ionisation detectors 14 bells and the required standby is 24 hours It will need to operate in alarm for hour Calculate the battery...

Page 15: ...ns bells 11 CLASS CHANGE Join terminals to activate sounders 12 FIRE RELAY NO CM NC Activates on fire including test mode 13 FAULT RELAY NO CM NC Normally powered ie NO is closed with no fault 14 BATT...

Page 16: ...AL 18 32 V SYSTEM VOLTAGE RIPPLE 2V PK PK MAX CHARGER SIZE UP TO 7AH in 24 Hours ZONE VOLTAGE 21V DC NOMINAL 20 22 5V SOUNDER ALARM OUTPUTS 2 x 400mA 24V DC Nominal AUXILIARY FAULT OUTPUT 1 x RELAY SE...

Reviews: