PREMIER SX INSTALLATION MANUAL.  

 

 

 

 

 

Approved Document No: GLT.MAN-101

 

 

 

PAGE 13

 

Issue : 1.95         Authorised: GH      Date: 09/06/2004

 

 

 

9.2 SYSTEM FAULT 
 

A system fault is an abnormal microprocessor running condition due to various unexpected 
phenomena  
 
This will result in the panel attempting to correct itself.  Should this fault occur, the System Fault LED, 
General Fault LED, General Fault relay and fault internal buzzer will be constantly active until the 
control keyswitch is turned from off position to control enable position.  This should cause this fault 
condition to reset. If not, consult your supplier 
 

9.3 SUPPLY FAULTS 

 
A power supply fault is indicative of one or more of the following faults: - 
 
1.Loss of Mains power – Remedy  
 
 

a. 

Check mains fuse (Conn 5).  Also, check that main power is present. 

 

b. 

Check charger fuse FS1. 

 
2.Loss of Battery power – Remedy 
 
 

a. 

Check battery fuse FS2. 

 

b. 

Check that battery connections are secure. 

 
3.Low Battery – Remedy 
 
 

a. 

Check battery voltage. 

 
4.Wrong Charging Voltage. 

The charging voltage should be 28.4V off load at 20

o

C. If it has been altered, reset using 

potentiometer VR1 

 
5. Overcharged Batteries. 

Remove the batteries and measure the voltage. If it is reading over 27.4 then the batteries 
are overcharged. Try to run the panel on batteries only for half an hour or so to try to 
discharge the batteries. If this doesn’t solve the problem, replacement batteries will be 
required. 

 

9.4 EARTH FAULTS 

 
An EARTH fault indicates that something is shorting to earth (usually through the cable screen). 
Disconnect the earth screens one at a time to determine the problem line. 
 
(Note: connecting other equipment , eg an oscilloscope , to the panel can give an earth fault) 
 
The voltage between battery –Ve and earth should be 14-16 volts. If it is not, the voltage should 
indicate what is shorting to earth. 

 

9.5 SOUNDER FAULTS 

 
Check that the correct END of Line resistor has been fitted. (10K – brown, black, orange, gold) 
 
Check that both fuses are OK (FS4 & FS5 – 400mA QB) 
 
If working on an existing installation, check that the devices are polarised. (See Page 5) 
 
Check cable continuity (remove from panel and measure continuity. Should read 10K)

Summary of Contents for NPSX1

Page 1: ...INSTALLATION MANUAL...

Page 2: ...X TO THE WALL 4 CONNECTING MAINS BATTERY POWER 8 4 1 CONNECTING MAINS POWER 4 2 CONNECTING THE BATTERIES 5 FIELD DEVICE TERMINATION 9 5 1 TERMINATING THE DETECTION AND ALARM SOUNDER CIRCUITS 5 2 AUXIL...

Page 3: ...ned with the property at an early stage in case he has any special requirements If in doubt read BS 5839 Pt 1 2002 Fire Detection and Fire Alarm Systems for buildings Code of Practice for System Desig...

Page 4: ...be paid to this fact Depending on the environment the cables may need mechanical protection such as a conduit 2 2 MAINS WIRING RECOMMENDATIONS The Mains supply to the FACP is fixed wiring using Fire r...

Page 5: ...e OUT to non stripe side of continuity diode Some makes will connect the ve to a 470R load resistor or a polarisation diode to enable the detector to work correctly Our new Fyreye detectors pronounced...

Page 6: ...ndition In a fault condition the output relay turns off to ensure failsafe operation even in the event of total power loss That is the normally open contact will be closed when there is no fault and o...

Page 7: ...oved but subsequently not used it should be covered up The 230Va c Mains cable must be fed into the enclosure via one of the cable entries at the top right corner of the back box Refer to Connecting t...

Page 8: ...nterference Once the mains is connected the protective cover should be replaced BEFORE turning on the mains power This will minimise the chance of electric shock from the PCB MAKE SURE ANY SPARE ENTRY...

Page 9: ...cable grounding plate The Detector and Sounder circuits should be connected to the appropriate connector block on the Termination PCB as shown in Figure 6 below All screens should be fed through the g...

Page 10: ...Alarm sounder outputs being activated can be programmed into the panel by the Engineer This is a particularly useful feature for schools nightclubs and other public places where the nuisance and panic...

Page 11: ...continue running but doesn t want spurious false alarms The panel will respond in the usual manner to any events in any non disabled zones 7 2 TO PROGRAMME ZONE OR SOUNDERS AS DISABLED Any number of...

Page 12: ...Zone or turn the control key switch to off position to exit test mode 9 GENERAL FAULT FINDING 9 1 ZONE FAULTS Open circuit faults will be indicated by zone s fault LED flashing In case of a short cir...

Page 13: ...Charging Voltage The charging voltage should be 28 4V off load at 20o C If it has been altered reset using potentiometer VR1 5 Overcharged Batteries Remove the batteries and measure the voltage If it...

Page 14: ...al Detector 0 0001 Amp 100 A Typical Example A system comprises of 20 ionisation detectors 14 bells and the required standby is 24 hours It will need to operate in alarm for hour Calculate the battery...

Page 15: ...ns bells 11 CLASS CHANGE Join terminals to activate sounders 12 FIRE RELAY NO CM NC Activates on fire including test mode 13 FAULT RELAY NO CM NC Normally powered ie NO is closed with no fault 14 BATT...

Page 16: ...AL 18 32 V SYSTEM VOLTAGE RIPPLE 2V PK PK MAX CHARGER SIZE UP TO 7AH in 24 Hours ZONE VOLTAGE 21V DC NOMINAL 20 22 5V SOUNDER ALARM OUTPUTS 2 x 400mA 24V DC Nominal AUXILIARY FAULT OUTPUT 1 x RELAY SE...